Power Supply and Distribution System Troubleshooting
- When a UPS is faulty, alarm information is displayed on the LCD. Critical alarms must be handled before powering on the UPS again. Otherwise, the fault may be extended, or the UPS may be damaged.
- If the fault is not rectified, contact Huawei technical support.
Symptom |
Possible Cause |
Measure |
---|---|---|
The power input to the downstream device is abnormal. |
|
|
The surge protection function fails. |
|
|
The general switch is ON, the LCD displays no information, and the system does not perform self-check. |
The input power supply is not connected. |
Check the UPS input power cable connection. |
The input voltage is less than the lower threshold or greater than the upper threshold. |
Use a voltmeter to check whether the UPS input voltage meets requirements. |
|
The mains is normal, but the AC input indicator is off. The UPS works in battery mode. |
The UPS mains switch is OFF. |
Turn on the UPS mains switch. |
The input cable is not properly connected. |
Check the UPS input power cable connection. |
|
The UPS fails to communicate. |
|
|
The UPS does not report a fault but has no output voltage. |
The output cable is not properly connected. |
Check the output power cable connection. |
The UPS does not start after you press |
|
Press |
The UPS is overloaded. |
Shut down all loads, and restart the UPS. |
|
The mains indicator is off. |
The mains voltage or frequency exceeds the UPS input range. |
Use a multimeter to verify that the input voltage and frequency meet specifications. |
The battery discharge time is obviously shorter than the standard time. |
Batteries are not fully charged. |
Charge batteries for more than 8 hours when the mains is normal. Test the discharge time again. |
The battery performance deteriorates. |
Contact your local Huawei technical support to replace batteries. |
|
Abnormal noise or smell is generated in the UPS cabinet. |
The UPS is faulty. |
Shut down the UPS and cut off the power input immediately. Contact your local Huawei technical support. |
The battery indicator blinks. The buzzer buzzes 1 second and then stops 1 second. The battery reserve is insufficient. The UPS is about to shut down. |
|
|
The user forgot the password. |
None |
|