Material: A spare cabinet electronic clasp lock is available and functional.
Context
cabinet electronic clasp locks are installed at the front and rear doors of a cabinet.
Procedure
Open the front or rear door of the cabinet.
Remove the signal cables from the cabinet electronic clasp lock.
Remove the cabinet electronic clasp lock bolts using a Phillips screwdriver.
Figure 6-1 Removing a cabinet electronic clasp lock
Install the new cabinet electronic clasp lock at the front or rear door of a cabinet.
Before removing a cabinet electronic clasp lock, remember the DIP switch settings on the cabinet electronic clasp lock. Ensure that the DIP switch settings on the new cabinet electronic clasp lock are the same as those on the old cabinet electronic clasp lock.
The mounting holes for the new cabinet electronic clasp lock are slotted holes. If the door cannot be properly closed after installation, adjust the lock height based on site requirements.
Reconnect the cables to the cabinet electronic clasp lock.
Replacing a Gas Spring
Prerequisites
Tools: Phillips screwdriver, step ladder
Material: A spare gas spring is available and functional.
Context
Gas springs are installed on the top of a cabinet.
Procedure
Open the front or rear door of the cabinet.
Remove the nuts from the gas spring using an adjustable wrench.
Remove the gas springs.
Figure 6-2 Removing a gas spring
Tighten the new air spring using an adjustable wrench.
Replacing a PDU2000
Prerequisites
Tools: Phillips screwdriver, step ladder
Material: A spare PDU2000 of the same model is available and functional.
Context
A PDU2000 is installed at the rear door of a cabinet.
Procedure
Open the rear door of the cabinet.
Switch off the output circuit breaker of the power distribution subrack for the PDU2000. Disconnect the power cables and signal cables from the PDU2000 terminal block.
Remove the bolts that secure the PDU2000 using a Phillips screwdriver.
Secure the new PDU2000 to the rear door of the cabinet.
Reconnect the power cables or signal cables to the PDU2000, and switch on the circuit breaker of the power distribution subrack.