System Functions
Monitoring
- Temperature and humidity monitoring: Detects and collects statistics on the ambient temperature and humidity inside the smart module; provides real-time alarm signals.
- Water leakage monitoring: Detects water leakage at the bottom of the smart module and provides real-time alarm signals.
- Smoke monitoring: Detects smoke in the smart module and provides real-time alarm signals.
- Power distribution monitoring:
- (In the intelligent power distribution scenario) Monitors the general mains input voltage, frequency, current, and power, as well as the UPS input voltage, frequency, current, and so on.
- (In the non-intelligent power distribution scenarios) Monitors the UPS input voltage, frequency, current, and so on.
- Smart cooling product monitoring:
- Monitors the supply and return air temperatures in real time.
- Allows you to set the return air temperature setpoint for a single product.
- Monitors and displays the fan speed, and displays the running percentage.
- Monitors and displays the compressor running status.
App View
- Generates a 2.5D layout view that matches the actual layout of the smart module, including the power distribution module, smart cooling product, and T/H sensor. In addition, the power resource usage (displayed only when the intelligent power distribution module is configured) and ambient temperature and humidity in the smart module are displayed on the home screen of the app.
- Allows you to view the power resource usage of the smart module and each cabinet (only when the intelligent power distribution module is configured).
- Displays the real-time status monitoring data and alarms of the aisle temperature and humidity on the floor plan.
- After logging in to the app installed on the PAD, you can open the cabinet door on the corresponding screen.
Alarm
- The system monitors the status of smart cooling products, power distribution, and environment. If a fault or parameter error occurs, the system generates an alarm in real time. You can view the alarm cause and solution in the alarm details.
- Alarms can be classified into four severities: critical, major, minor, and warning. The alarm severities can be user-defined.
- Active alarms can be filtered by device and alarm severity.
- Alarm notifications can be sent by email and SMS.
- A maximum of 500 concurrent active alarms are supported.
Historical Data Query
- Historical alarm: You can view the alarms that have been generated in the system. The historical alarm information includes the device name, alarm name, alarm severity, alarm generation time, and alarm clearance time.
- Performance data statistics: You can view historical data of devices to help analyze data or problems.
- Operation log: You can view logs of key operations, such as user login, parameter modification, data export, device upgrade, and access control events.
- Data export: You can export historical data of the ECC800-Pro and some southbound devices.
Linkage Control
- Supports the linkage logic of aisle smoke alarms or high temperature alarms. By default, the cabinet doors are opened through linkage by default.
Aisle smoke alarms cannot trigger the customer's fire extinguishing system. Only dry contact alarm signals are provided.
- Supports the aisle emergency ventilation linkage logic. The cabinet doors are opened by default under linkage.
- If the protected area of the fire extinguishing system is inside the smart module, when a smoke alarm is generated, the door of the linked cabinet does not open. If the door is opened, an alarm (door open alarm) is generated.
- If the protected area of the fire extinguishing system is outside the smart module, when a smoke alarm is generated, the rear door of the linked cabinet is opened.