Alarm References
This chapter provides only measures to clear major and critical alarms for certain components. For details about other alarms, see the ECC800-Pro WebUI.
Component |
Alarm Name |
Alarm Severity |
Possible Cause |
Measures |
---|---|---|---|---|
Surge protective device (SPD) |
SPD fault |
Major |
A surge protection module is damaged or the SPD circuit breaker has tripped. |
Replace the surge protection module or switch on the SPD circuit breaker. |
UPS |
Rectifier fault |
Critical |
|
|
Internal fault |
Critical |
The bypass input cable connection does not match the output system. |
Correct the bypass input cable connection so that it matches the output system. |
|
Fan fault |
Critical |
The fan is abnormal. |
Clean up foreign matter around the fan. If the fault persists, contact Huawei technical support. |
|
Inverter fault |
Critical |
The inverter output short-circuits. |
Eliminate the short circuit at the output port cable connection, and then power on and start the inverter again. If the fault persists, contact Huawei technical support. |
|
Output short circuit NOTE:
The system immediately disconnects the power output. |
Critical |
The load or cable is short-circuited. |
Locate and rectify the short circuit. |
|
Intelligent lithium battery monitoring system |
Communication Failure |
Critical |
The network cable communication is interrupted. |
Check the cable connection to the smart ETH gateway. |
BCB Tripping |
Critical |
|
Identify the alarm cause, rectify the fault, and switch on the BCB box. |
|
Single Batt. terminal off |
Critical |
|
|
|
Single Batt. Exception |
Critical |
|
|