Quarterly Maintenance
Maintenance Area |
Maintenance Item |
Operation |
Expected Result |
Troubleshooting |
---|---|---|---|---|
Power supply and distribution system |
Operating status of the surge protection module |
Check the surge protection module indicator and MCB status. |
|
|
UPS |
Operating environment |
- |
|
|
LCD |
- |
According to the status icons on the LCD, all units are operating properly. No fault or alarm information is found in the active and historical alarm records. |
If an alarm is present, rectify the fault by checking the device status and parameters. |
|
Cleanliness |
- |
Wipe the cabinet surface using a white paper and the paper does not turn black. |
Remove the dust, especially from the air filter on the front door, or replace the air filter. |
|
Parameter configuration |
- |
The configuration of the output voltage grade, frequency, number of batteries, and battery capacity meets requirements. |
Reset the parameters. |
|
Power cables and terminals (between the UPS and the power distribution subrack) |
- |
The insulation layer of cables is intact and terminals are free from noticeable sparks. |
|
|
Lithium battery |
Battery management alarm |
- |
No battery management alarm is generated. |
Identify the cause of an alarm based on the alarm information. |
Battery appearance |
- |
|
If the battery appearance is abnormal, contact Huawei technical support. |
|
Battery operating temperature |
- |
|
|
|
Battery management parameter settings |
- |
Check that the settings of battery management parameters meet the requirements in the user manual. |
Set parameters correctly. |
|
Battery bolts |
- |
The location of the signs marked on battery terminal bolts indicating tight connections does not change. |
Take photos from multiple angles and contact Huawei technical support. |
|
Cables between batteries |
- |
No cable deteriorates and the insulation layer does not crack. |
Replace the faulty cable. |
|
Battery voltage |
- |
|
|
|
Shallow discharge test (recommended) |
- |
Conduct a shallow discharge test when the UPS is backed up to verify that the batteries can discharge properly. |
|
|
ECC800-Pro |
AC input |
- |
Input voltage: 200–240 V AC Frequency: 45–55 Hz |
If the input voltage is abnormal, check the power grid status and input cable connection. |
Output voltage |
- |
Output voltage: 53.5 V DC±5% |
If the output voltage is abnormal, check the load power and cable connection. |
|
Indicator |
- |
The indicator on the power module is steady green. |
Check the output voltage and determine whether the power module is faulty. If the power module is faulty, replace it. |
|
Fan |
- |
No abnormal noise is generated. |
If abnormal noise is generated, clean the fan. |
|
Operating environment |
- |
|
If the temperature or humidity is abnormal, check the smart cooling product status. |
|
Monitoring module indicator |
- |
The monitoring module indicator is steady green or blinking green. |
If the indicator is off or any abnormal condition occurs, see Management System Troubleshooting to rectify the fault. |
|
Network interface indicator |
- |
The green indicator is steady on, and the yellow indicator is blinking. |
If the indicator status is abnormal, check the network cable connection. |
|
Monitor interface (network management system or WebUI) |
- |
Export smart cooling product logs, alarms, temperature and humidity data, as well as the operating status and time of the water sensor, temperature sensor, and smoke sensor from the management system. View the historical alarms generated in this quarter and select the most common five ones. |
If an alarm is generated, handle the alarm by referring to Management System Troubleshooting and Alarm References or contacting Huawei technical support. |
|
Cable connection |
- |
The cable connection is secure. |
Secure loose cables. |
|
- |
Cables are not damaged. |
Replace damaged cables. |
||
Camera |
Camera availability |
On the ECC800-Pro WebUI, choose to enter the video view page. Type the camera name or IP address to find the camera, and click to view the real-time monitoring page. |
The monitoring page is properly displayed after you click . |
If the monitoring page is not displayed after you click Replacing a Camera. , check that the IP address is correctly set, and check cable connections or replace the camera. For details, see |
Intelligent lithium battery monitoring system |
Battery management alarm |
- |
No battery management alarm is generated. |
Identify the cause of an alarm based on the alarm information. |
Cleanliness |
- |
Wipe the battery surface using a piece of white paper and the paper does not turn black. |
Remove dust. |
|
Battery connection |
- |
Battery terminals and cables are in good contact. |
Locate poor contact points between battery terminals and cables. |
|
Measurement of the ambient temperature of the intelligent battery monitoring system |
- |
The ambient temperature of the intelligent battery monitoring system is lower than 45°C. |
Locate the cause of an abnormal temperature. |
|
Water sensor and water detection cable |
Functions of the water sensor and water detection cable |
Place the water detection cable into the water and check whether a water leakage alarm is generated by the water sensor. |
A water leakage alarm is generated. |
If a water leakage alarm is not generated, replace the water detection cable. |