No relevant resource is found in the selected language.
Your browser version is too early. Some functions of the website may be unavailable. To obtain better user experience, upgrade the browser to the latest version.
Huawei uses machine translation combined with human proofreading to translate this document to different languages in order to help you better understand the content of this document.
Note: Even the most advanced machine translation cannot match the quality of professional translators.
Huawei shall not bear any responsibility for translation accuracy and it is recommended that you refer to the English document (a link for which has been provided).
Adding a UPS2000G
Adding a UPS2000G
Prerequisites
One end of the straight-through cable has been connected to the RS485 port on the UPS2000G, and the other end has been connected to the COM4 port on the ECC800-Pro.
Procedure
Add a UPS2000G-L.
Log in to the ECC800-Pro WebUI as an administrator.
Add a UPS2000G-L.
Table 5-6 Adding a UPS2000G-L
Path
Parameter
Setting
Choose System Settings > Device Management and click Add Device. The parameters for adding devices are displayed.
Device attribute
Select UPS from the drop-down list box.
Device Type
Select UPS2000G-L from the drop-down list box.
Connect To
Select ECC800 from the drop-down list box.
Communications Port
Select COM4 from the drop-down list box.
NOTE:
The setting example indicates that the UPS2000G is connected to the COM4 port on the ECC800-Pro. If the UPS2000G is connected to another port, enter the number of the connected port.
Device Address
In this example, Device Address is set to 1. During actual configuration, set the device address for the UPS2000G-L based on the actual situation.
Click Test Connect to check whether the UPS2000G-L connects to the ECC800-Pro properly.
If the connection succeeds, click Confirm. The connected devices are displayed in the Number of connected devices list.
If the connection fails, check whether the device is properly connected to the ECC800-Pro, whether the device and ECC800-Pro are running properly, and whether the parameter settings are consistent with the device parameters.