Installing a Cabinet
Installing a Cabinet
Prerequisites
The floor levelness meets engineering requirements.
Context
To position a cabinet, perform the following steps:
Determine the position of the cabinet based on the engineering layout diagram.
Place the cabinet at the correct installation position.
Procedure
Determine the cabinet position based on the engineering layout diagram.
Place the cabinet at the correct installation position.
Level the cabinet using a wrench.
Use a measuring tape to check that the vertical distance between the top of the 2000 mm high cabinet and the floor is 2000 mm (+3 mm). Then use a level to check that the cabinet is level.
If the leveling height of the cabinet does not meet the requirements, the cabinet cannot be opened or closed properly.
To ensure the cabinet steadiness, adjust all the six anchor bolts at the bottom of the cabinet in place.
After leveling the anchor bolts in the first and last rows, use a flat-head screwdriver to level the anchor bolts in the middle row until they are in close contact with the ground.
Do not remove the anchor bolts. Otherwise, rework is required if the cabinet height does not meet requirements.
Anchor bolt adjustment method: Wrench an anchor bolt clockwise to elevate a cabinet leg, or wrench an anchor bolt anticlockwise to lower it. The anchor bolts can be adjusted within a range of 0-8 mm.
Levelness check standard: Ensure that the cabinet is level in width and depth directions when leveling the cabinet. Put a level at the bottom of the cabinet in width and depth directions and check that the air bubble is in the middle between the two lines marked on the glass tube.