UPS Power-On Commissioning
- Switch on the external battery circuit breaker (if any).
- Press ON/MUTE to start the UPS. The UPS will enter the standby mode. Press and hold SELECT for 1s on a non-setting screen to access the login screen for parameter settings. The initial password is 000001. Enter the correct password to enter the UPS setting mode.Figure 5-1 Standby mode
- Setting the output voltage based on site requirements
Output Voltage
Description
You need to shut down the inverter before changing the output voltage.
220: indicates that the output voltage is 220 V AC.
230: indicates that the output voltage is 230 V AC (default value).
240: indicates that the output voltage is 240 V AC.
- Set the battery capacity.
Battery Capacity
Description
- Default value: 100 Ah
- Value range: 50–2400 Ah. The value increases by 50 Ah each time you press SELECT.
- Press and hold ON/MUTE for more than 5s. Release the button when you hear a beep sound. The UPS starts to work in battery mode.Figure 5-2 Battery mode
- After you ensure that the UPS runs properly, switch on the AC output circuit breaker Q for the UPS to start the load.