(Optional) NetEco Management
Data Center Management
Setting NetEco Parameters
Procedure
- Apply for a fixed IP address to the equipment room network administrator.
- Set the IP address, subnet mask, and default gateway on the ECC800-Pro WebUI.Table 5-18 IP parameters
Path
Parameter
Default Value
Setting
IP
192.168.8.10
Set this parameter based on the IP address assigned by the network administrator.
Subnet mask
255.255.255.0
Set this parameter based on the subnet mask assigned by the network administrator.
Default gateway
192.168.8.1
Set this parameter based on the default gateway address assigned by the network administrator.
- Click Submit.
- Set NetEco communications parameters and authentication password on the ECC800-Pro WebUI.Table 5-19 NetEco parameters
Path
Parameter
Default Value
Setting
Server IP
192.168.8.11
IP address of the primary NetEco server
NOTE:The NetEco IP address and the ECC800-Pro IP address must be configured in the same network to ensure normal connection between the NetEco and the ECC800-Pro.
Port number
31220
31220
Network port for link setup
WAN_1
WAN_1
Table 5-20 Setting an authentication passwordPath
Parameter
Default Value
Setting
Authentication password
Modifyme_123
Set this parameter based on customer requirements.
NOTE:Requirements for setting passwords:
'a~z','A~Z','0~9','~!@#^*_={}:,./?-`$'(8-32 characters that include at least three of the following types: lowercase letters, uppercase letters, digits, and special characters)
Confirm authentication password
-
-
- Click Submit.
Powering On a Server
This topic describes how to power on a server.
Procedure
- Check that the power cables and ground cables of the upstream components of the server are securely connected with correct polarity and in good contact.
- Ensure that the upstream input power supply is not connected. Use a multimeter to measure the resistance between the upstream output power supplies and between the working ground and the protection ground. It is required that short circuit not occur between power outputs or between the BGND and PGND.
- Turn on the switch for the upstream power supply of the server.
- Press the power button on the chassis of the server to power on the server.
After the server is started properly, the button/indicator of its power switch is displayed green.
Figure 5-17 Power button on the 2288X V5 serverFigure 5-18 TaiShan 200 server power button
Logging In to the NetEco Client
This section describes how to log in to the NetEco client using a web browser.
Prerequisites
- The network connection between your PC and the client IP address of the NetEco is normal and the function of the O&M plane are running properly.
- You have obtained the user name and password for login.
Procedure
- In the browser address box, enter https://IP address of the NetEco server:31943, and then press Enter.
- 192.168.8.11 is the default IP address of the NetEco.
- Latest Chrome (Stable Channel) and Firefox (ESR Release) are recommended.
You are advised to set the display resolution as 1920 x 1080 or higher.
Make sure that the IP address of the NetEco server is not contained in the compatibility view website.
- Enter the User Name, Password, and click Login.
The preset user of NetEco is admin, the preset password is Changeme_123. This user has all the operation rights on the managed objects. After the first login, change the password in time to ensure account security and prevent unauthorized network attacks, such as data tampering. Huawei will not be liable for any security issues caused by your failure to change the preset password in time or password loss after changing.
If the number of online users reaches the maximum number supported by the system, a message is displayed, indicating that you cannot log in. In this case, contact the system administrator.
After you enter the incorrect password for three consecutive times, you must enter the verification code upon the fourth login. After you enter the incorrect password for five consecutive times, the user account or the IP address is locked for 10 minutes.
Loading the NetEco Software License
Installing NE Adapters
Install the NE adapters on the NetEco.
Prerequisites
You have obtained the adapter software installation packages.
Procedure
- Choose .
- In the navigation tree on the left, choose Adapter Management and click Upload.
- On the page that is displayed, click + to select the file to be uploaded.
- Click Upload to upload the files.
- Select the NE adapter packages to be installed on the Adapter Management page, and click Install. Then, click Yes in the displayed dialog box.
The time required for the installation is related to the number of adapters. Wait for the installation to complete.
General Operation: Adding a Management Domain
This section describes how to create a management domain.
Context
- The management domains include Park, Building, Room, ContainerDC, Subnet, NetecoSite, FusionModule500, Modular, Room-ShapeNode, and Building-ShapeNode. You are advised to plan the subordinate relationship between management domains and devices before performing operations.
- The NetEco is preconfigured with management domains such as cabinets, battery cabinets, buildings, containers, floors, FusionModule500, smart modules, NetEco sites, parks, PDUs, equipment rooms, and subnets. To use more management domains, you need to install the corresponding adapter software package on the NetEco.
Procedure
- Log in to the NetEco client.
- On the main menu, choose Device Management > Configuration > Planning Configuration.
- Choose the upper-layer node of the management domain to be added in the navigation tree on the left.
- In the Domain area on the lower left of the page, drag a management domain icon to the required position in the planning configuration area.
You can adjust the shape of Room, Room–ShapeNode, Building–ShapeNode, Floor–ShapeNode, Container–ShapeNode, and NetecoSite by:
- Hold down Shift and click the frame to add a yellow dot.
- Click and move the yellow dot to design an irregular polygon.
- To delete a management domain, click the domain icon and select Delete under
.
- In the right side of the view area, set Management Info.
You can configure Management Info, Electricity Info, and Refrigeration Info for the equipment room management domain.
- Click
on the toolbar to save the settings.
- Repeat steps 3 to 6 until the configuration is complete.
Example: Adding a Smart Module
This section describes how to create a module in the root node, subnet, equipment room, container, or site management domain.
Procedure
- Log in to the NetEco client.
- On the main menu, choose Device Management > Configuration > Planning Configuration.
- Choose the management domain where you want to add a smart module from the navigation tree on the left.
- In the Domain area on the lower left of the page, select Modular from the drop-down list box.
- Select the Modular to be added and drag the modular icon to the management domain area.Figure 5-19 Adding the smart module in the room area
- Modify Management Info of the smart module as required or retain the default values.
- Click
on the toolbar to save the settings.
Follow-up Procedure
Related Operations |
Procedure |
---|---|
Delete modules |
You can delete one module or multiple modules in batches on the current page.
NOTE:
If a module contains subdevices, you cannot delete it. You can delete the module only after you delete subdevices in the module.
|
Add tools |
|
Creating an ECC800-Pro on the NetEco
Prerequisites
- You have logged in to the NetEco client by web browser.
- You have created modules in Data Center Planning.
Context
For detailed operations, see iManager NetEco 6000 Device Installation and Commissioning Guide of the corresponding version.
Procedure
- Choose System > Configuration > Data Center Planning from the main menu. The Data Center Planning window is displayed.
- Click
in the upper left area of the Data Center Planning window.
- Click Access switch to the Add Device window. You can add an ECC800-Pro device to the specified modular in the Add Device window.Figure 5-21 Adding an ECC800-Pro device to the modular
Click OK, and you can view the task information, including Type, Device Name, Region, Progress, Status, Start Time, End Time, and Information in the displayed Progress window.