Installation Environment Check
Check Item |
Specifications |
Check Result |
---|---|---|
Operating temperature |
Indoor operating temperature range: 0°C to 40°C |
□ Passed □ Failed |
Operating humidity |
5%–95% RH |
□ Passed □ Failed |
Physical environment of the equipment room |
The interior is clean and tidy, free from dust and conductive pollution. |
□ Passed □ Failed |
Altitude |
0–4000 m (The power is derated as described in IEC 62040-3 when the altitude exceeds 1000 m.) |
□ Passed □ Failed |
Levelness |
Allowed deviation: 3/2000 mm |
□ Passed □ Failed |
Equipment room height |
≥ 2.6 m |
□ Passed □ Failed |
Equipment room area |
≥ 10.15 m2 |
□ Passed □ Failed |
Equipment room maintenance clearance |
At least 1200 mm, 1000 mm, and 1000 mm maintenance clearance should be reserved from the front door, rear, and side of the cabinet, respectively. At least 100 mm clearance should be reserved from the wall. |
□ Passed □ Failed |
Power system |
208–240 V 1Ph 50 Hz/60 Hz |
□ Passed □ Failed |
Water port |
Condensate drain outlet: Drains condensate water from the smart cooling product. |
□ Passed □ Failed |
If any of the requirements is not met, contact Huawei technical support.