Verifying the Installation
Check the cabinet installation against the items listed in Table 8-20. Take appropriate measures for the disqualified items immediately.
No. |
Check Item |
Check Result |
---|---|---|
1 |
Labels on the cabinet are clear and properly pasted. |
- |
2 |
Screws for securing the cabinet are properly installed. |
- |
3 |
Rotate the exhaust valve bonnets on the top of the air/liquid heat exchanger clockwise until they cannot be rotated to ensure that the bonnets are tightened after the first use. |
- |
4 |
The branch hose is not excessively bent or dented, and the end connector is free from defects such as sharp bends. |
- |
5 |
Branch valves of the liquid-cooled cabinet are open. |
- |
6 |
The entire liquid cooling loop has no leakage or condensation after water is supplied. |
- |
7 |
Paint on the cabinet is not scraped or the surface is not stained. If not, apply paint or clean up the stains. |
- |
8 |
The instructions and accessories delivered with the equipment are intact. |
- |
Check installation of cables against the items listed in Table 8-21. Take appropriate measures for the disqualified items immediately.
No. |
Check Item |
Check Result |
---|---|---|
1 |
Cables are properly routed in the cabinet, complying with Huawei's cable layout specification. |
- |
2 |
Power cables and protection ground (PGND) cables are properly connected. |
- |
3 |
PGND cables and power cables are in good condition without any splice. |
- |
4 |
Power cables, PGND cables, and signal cables are independently bundled. The pitches between power cables and signal cables as well as between PGND cables and signal cables meet the requirements. |
- |
5 |
Cables are not routed on the dissipation holes of devices. |
- |
6 |
Cables are bundled in uniform spacing with appropriate tightness. |
- |
7 |
The bending radius at the corner meets the specifications. |
- |
8 |
The installed cables do not block the indicators or hinder replacement of components. |
- |
9 |
Unused optical cable connectors are covered by protective caps. Unused optical modules are covered by dust covers. |
- |