FAQ-What are Cable Power Supply and Cable Size of NE80E Device

Publication Date:  2012-07-27  |   Views:  142  |   Downloads:  0  |   Author:  Wu Jie  |   Document ID:  EKB0000240498

Contents

Issue Description

Q:
What are cable power supply and cable size of NE80E device?

Alarm Information

Null

Handling Process

A:
According to the whole technical demands of YD/T 1051-2000 communication site power system, the lowest input voltage of communication device is -40V. The voltage drop from power system to the cable of communication device is 3.2V.
For communication device with the lowest voltage -40V, the voltage from storage battery to the device is 3.2V. V1+V2+V3+V4+V5=3.2V. It requires V1/0.5V, V2/0.4V, V3/1.2V and V4/0.5V. According to the computation of voltage drop 3.2V, the voltage drop V5 from PDF to communication device is 0.6V.
The lowest input voltage of NE80E&NE5000E device is -38V. The roundtrip voltage drop from PDF to NE80&NE5000 device △U=V5+ (40-38) V=0.6+2V=2.6V.
For NE5000E, the maximum input current is 132A and the maximum input cable cross-sectional area is 50 �, △U=V5+(40-38)=2.6V. The remotest transmission distance is 50 �.  
50=132×L/57×2.6  L56m is roundtrip distance. NE5000E chooses 50 � cable and power distribution is 28m.

Root Cause

Null

Suggestions