FAQ-Battery Over Curr alarm generate, what should be done

Publication Date:  2014-10-30  |   Views:  1061  |   Downloads:  0  |   Document ID:  EKB1000058370

Contents

Issue Description

Battery Over Curr alarm generate, what should be done?

Solution

Possible Causes:
1) The rectifier communication is interrupted.
2) Poor contact of the SMU.
3) The SMU is faulty.

Measures:

1) Check whether an alarm is generated for rectifier communication interruption. If yes, remove the rectifier and reinstall it to check whether the alarm is cleared. If the alarm still exists, replace the rectifier.

2) Remove the SMU and reinstall it to check whether the alarm is cleared. If the alarm still exists, replace the SMU.