PowerCube 500 V200R001C10 User Manual (CPS300-N18A1H)

This document describes the PowerCube 500 solution in terms of its overview, components, LIVE APP, preventive maintenance, alarm handling, troubleshooting, and component replacement.

Function Module (CPS300-N18A1H)

Function Module (CPS300-N18A1H)

Functions

The function module integrates power unit (power rectification and distribution) and a network equipment. It converts AC power or DC solar power into stable 12 V DC, 24 V AC, and 53 V DC power, generates fault alarms, and reports monitoring data to the upstream network management system (NMS) in real time.

Appearance

Figure 3-1 Function module

Indicators

Figure 3-2 Indicators on the function module

(1) Run indicator

(2) Alarm indicator

(3) Fault indicator

Table 3-1 Function module indicator description

Indicator

Color

Status

Remarks

Run indicator

Green

Off

The function module has no power input or is faulty.

Blinking slowly (0.5 Hz)

The function module is communicating properly with upstream monitoring equipment.

Blinking fast (4 Hz)

The function module fails to communicate with upstream monitoring equipment.

Alarm indicator

Yellow

Off

There is no alarm.

Blinking slowly

The function module has generated an alarm, which can be cleared.

Steady on

The function module has generated an AC power failure or PV array fault alarm, which can be cleared.

Fault indicator

Red

Off

The function module is normal.

Blinking slowly

The function module has an external fault, which can be cleared.

Steady on

The function module has an internal fault, which cannot be cleared.

NOTE:

The three indicators are steady on when the function module is upgrading. They return to normal status after the upgrade is complete.

Panel

Figure 3-3 CPS300-N18A1H panel (front view)

(1) Fiber splice tray

(2) RS485 port (northbound)

(3) 53 V DC power port

(4) 12 V DC power port

(5) 24 V AC power port

(6) Dry contact output/input ports

(7) Fast Ethernet (FE) port

(8) RS485 port (reserved)

  
Figure 3-4 CPS300-N18A1H panel (bottom view)

(1) Cable outlets

(2) AC input port

(3) BAT port

(4) Solar input port

(5) COM_CAN port

(6) Antenna port

(7) Ground screw

     

Ports

Table 3-2 Port description

Port Type

Silk Screen

Remarks

Communications port

RS485 (northbound)

The RS485 port is used to communicate with northbound equipment.

Baud rate: 9600 bit/s by default

Communications protocol: Modbus

COM_CAN

The COM_CAN port is used to communicate with a cascaded lithium battery.

Baud rate: 125 kbit/s

Communications protocol: control area network (CAN)

RS485 (reserved)

The RS485 port is used to communicate with southbound equipment.

Baud rate: 9600 bit/s by default

Communications protocol: Modbus

FE

The FE port is used to communicate with the OSS.

Communications parameter: 10M/100M autonegotiation

Communications protocol: SNMP

Figure 3-5 COM_CAN port pins
Table 3-3 COM_CAN port pin definitions

Pin

Signal Name

Description

1–4 and 6

Reserved

Reserved

5

BMS_ON+

Lithium battery presence signal

7

BMS_ON-

8

CANH

CAN data transmission and reception H

9

CANL

CAN data transmission and reception L

Table 3-4 RS485 (northbound) port pin definitions

Pin

Signal

Remarks

1

RS485+

RS485 data +

2

RS485_GND

RS485_GND

3

RS485-

RS485 data –

Table 3-5 RS485 (reserved) port pin definitions

Pin

Signal

Remarks

1 and 4

GND

Ground

2

RS485+

RS485 data +

3

RS485-

RS485 data –

WiFi Function

You can locally access the WebUI using WiFi.

  • You are advised to periodically change the WiFi password to improve account security and prevent unauthorized network attacks, such as data tampering.
  • Huawei will not be liable for any loss caused by your failure to change the password in time or to keep the new password properly.

Change the WiFi account password: choose System Settings > Network Config > WIFI.

Translation
Favorite
Download
Update Date:2019-11-01
Document ID:EDOC1000150171
Views:67041
Downloads:948
Average rating:5.0Points