PowerCube 500 V200R001C10 User Manual (CPS300-N18A1H)
This document describes the PowerCube 500 solution in terms of its overview, components, LIVE APP, preventive maintenance, alarm handling, troubleshooting, and component replacement.
Function Module (CPS300-N18A1H)
Functions
The function module integrates power unit (power rectification and distribution) and a network equipment. It converts AC power or DC solar power into stable 12 V DC, 24 V AC, and 53 V DC power, generates fault alarms, and reports monitoring data to the upstream network management system (NMS) in real time.
Appearance
Indicators
(1) Run indicator |
(2) Alarm indicator |
(3) Fault indicator |
Indicator |
Color |
Status |
Remarks |
---|---|---|---|
Run indicator |
Green |
Off |
The function module has no power input or is faulty. |
Blinking slowly (0.5 Hz) |
The function module is communicating properly with upstream monitoring equipment. |
||
Blinking fast (4 Hz) |
The function module fails to communicate with upstream monitoring equipment. |
||
Alarm indicator |
Yellow |
Off |
There is no alarm. |
Blinking slowly |
The function module has generated an alarm, which can be cleared. |
||
Steady on |
The function module has generated an AC power failure or PV array fault alarm, which can be cleared. |
||
Fault indicator |
Red |
Off |
The function module is normal. |
Blinking slowly |
The function module has an external fault, which can be cleared. |
||
Steady on |
The function module has an internal fault, which cannot be cleared. |
The three indicators are steady on when the function module is upgrading. They return to normal status after the upgrade is complete.
Panel
(1) Fiber splice tray |
(2) RS485 port (northbound) |
(3) 53 V DC power port |
(4) 12 V DC power port |
(5) 24 V AC power port |
(6) Dry contact output/input ports |
(7) Fast Ethernet (FE) port |
(8) RS485 port (reserved) |
(1) Cable outlets |
(2) AC input port |
(3) BAT port |
(4) Solar input port |
(5) COM_CAN port |
(6) Antenna port |
(7) Ground screw |
Ports
Port Type |
Silk Screen |
Remarks |
---|---|---|
Communications port |
RS485 (northbound) |
The RS485 port is used to communicate with northbound equipment. Baud rate: 9600 bit/s by default Communications protocol: Modbus |
COM_CAN |
The COM_CAN port is used to communicate with a cascaded lithium battery. Baud rate: 125 kbit/s Communications protocol: control area network (CAN) |
|
RS485 (reserved) |
The RS485 port is used to communicate with southbound equipment. Baud rate: 9600 bit/s by default Communications protocol: Modbus |
|
FE |
The FE port is used to communicate with the OSS. Communications parameter: 10M/100M autonegotiation Communications protocol: SNMP |
Pin |
Signal Name |
Description |
---|---|---|
1–4 and 6 |
Reserved |
Reserved |
5 |
BMS_ON+ |
Lithium battery presence signal |
7 |
BMS_ON- |
|
8 |
CANH |
CAN data transmission and reception H |
9 |
CANL |
CAN data transmission and reception L |
Pin |
Signal |
Remarks |
---|---|---|
1 |
RS485+ |
RS485 data + |
2 |
RS485_GND |
RS485_GND |
3 |
RS485- |
RS485 data – |
Pin |
Signal |
Remarks |
---|---|---|
1 and 4 |
GND |
Ground |
2 |
RS485+ |
RS485 data + |
3 |
RS485- |
RS485 data – |
WiFi Function
You can locally access the WebUI using WiFi.
- You are advised to periodically change the WiFi password to improve account security and prevent unauthorized network attacks, such as data tampering.
- Huawei will not be liable for any loss caused by your failure to change the password in time or to keep the new password properly.
Change the WiFi account password: choose System Settings > Network Config > WIFI.