Technical Specifications
Efficiency
Item |
Specifications |
---|---|
Maximum efficiency |
99.00% |
CEC efficiency |
98.50% |
Input
Item |
Specifications |
---|---|
Maximum input voltage |
1500 V |
Maximum input current (per MPPT) |
22 A |
Maximum short-circuit current (per MPPT) |
40 A |
Maximum backfeed current to the PV array |
0 A |
Minimum operating/startup voltage |
600 V/650 V |
Operating voltage range |
600–1500 V |
Full-load MPPT voltage range |
880–1300 V |
Rated input voltage |
1080 V |
Number of inputs |
12 |
Number of MPPT circuits |
6 |
Output
Item |
Specifications |
---|---|
Rated active power |
100 kW |
Maximum apparent power |
100 kVA at 40ºC; 90 kVA at 50ºC |
Maximum active power (cosφ = 1) |
100 kW |
Rated output voltage |
800 V AC, 3W+PE |
Rated output current |
72.9 A |
Supported power grid frequency |
60 Hz |
Maximum output current |
72.9 A |
Power factor |
0.8 leading to 0.8 lagging |
Maximum total harmonic distortion (rated power) |
< 3% |
Protection
Item |
Specifications |
---|---|
Input DC switch |
Supported |
Anti-islanding protection |
Supported |
Output overcurrent protection |
Supported |
Input reverse connection protection |
Supported |
PV string fault detection |
Supported |
DC surge protection |
Type II |
AC surge protection |
Type II |
Insulation resistance detection |
Supported |
RCMU |
Supported |
Typical Noise Value
Item |
Specifications |
---|---|
Typical noise value |
55 dB(A) |
The typical noise value is the test result obtained under typical working conditions in a lab. To avoid complaints, do not install the inverter in a noise-sensitive area.
Display and Communication
Item |
Specifications |
---|---|
Display |
LED indicator; USB data cable + App |
RS485 |
Supported |
MBUS |
Supported |
General Specifications
Item |
Specifications |
---|---|
Dimensions (W x H x D) |
1075 mm x 605 mm x 310 mm (42.32 in. x 23.82 in. x 12.20 in.) |
Net weight |
About 77 kg (169.76l b) |
Operating temperature |
–25ºC to +60ºC (–13°F to +140°F) |
Cooling mode |
Natural convection |
Maximum operating altitude |
4000 m (13123 ft) |
Relative humidity |
0–100% RH |
Input terminal |
Staubli MC4 |
Output terminal |
Cable gland + cable clip |
Overvoltage category |
II (DC)/III (AC) |
IP rating |
Type 4X |
Protection level |
I |
Pollution degree |
III |