TaiShan X6000 Server User Guide 05

Physical and Environmental Specifications

Physical and Environmental Specifications

Table 11-4 provides the physical and environmental specifications of the X6000.

Table 11-4 Physical and environmental specifications

Item

Specifications

Temperature

  • Operating temperature: 5°C to 35°C (41°F to 95°F)
  • Storage temperature (within 3 months): –30°C to +60°C (–22°F to +140°F)
  • Storage temperature (within 6 months): –15°C to +45°C (5°F to 113°F)
  • Storage temperature (within 1 year): –10°C to +35°C (14°F to 95°F)
  • Maximum temperature change rate: 20°C (36°F) per hour, 5°C (9°F) per 15 minutes
NOTE:

When a single fan fails, the server node supports the operating temperature ranging from 5°C to 30°C (41°F to 86°F).

Relative humidity (RH, non-condensing)

  • Operating humidity: 8% to 90%
  • Storage humidity (within 3 months): 8% to 85%
  • Storage humidity (within 6 months): 8% to 80%
  • Storage humidity (within 1 year): 20% to 75%
  • Maximum humidity change rate: 20% per hour

Altitude

  • Operating altitude: ≤ 3000 m (9842.52 ft)
    NOTE:

    When the server is used at an altitude from 900 m (2952.76 ft) to 3000 m (9842.52 ft), the highest operating temperature decreases by 1°C (1.8°F) for every increase of 300 m (984.25 ft).

  • HDDs are not supported at an altitude of over 3000 m (9842.52 ft).

Vibration

One cyclical sweep in each axial direction at the rate of 0.1 oct/min, with a total of three axial directions

5 Hz to 10 Hz: 5 mm (0.20 in., peak-to-peak value)

10 Hz to 100 Hz: 1 m/s2

Shock

Half sine wave, peak acceleration of 2 G, 11 ms, 3 times for each surface, and a total of three axial directions

Acoustic noise

The following data is the declared A-weighted sound power levels (LWAd) and declared average bystander position A-weighted sound pressure levels (LpAm) when the server is operating at 23°C (73.4°F). Noise emissions are measured in accordance with ISO 7779 (ECMA 74) and declared in accordance with ISO 9296 (ECMA 109).

Operating:

  • LWAd: 7.4 Bels
  • LpAm: 57 dBA
NOTE:

The actual sound levels generated when the server is operating vary depending on the server configuration, workload, and ambient temperature.

Corrosive air pollutant

  • Corrosion rate of the copper test piece: < 300 Å/month (in compliance with the ANSI/ISA-71.04-2013 gaseous corrosion level G1).
  • Corrosion rate of the silver test piece: < 200 Å/month.

Particulate pollutant

  • The ISO14664-1 Class 8 requirements are met.

    You are advised to ask a professional organization to monitor particulate pollutants in the equipment room.

  • There is no explosive, conductive, magnetic, or corrosive dust in the equipment room.
Translation
Favorite
Download
Update Date:2022-10-11
Document ID:EDOC1100048073
Views:121098
Downloads:166
Average rating:0.0Points

Digital Signature File

digtal sigature tool