SUN2000-(196KTL-H0, 200KTL-H2, 215KTL-H0) User Manual

M:SUN2000-196KTL-H0,SUN2000-200KTL-H2,SUN2000-215KTL-H0;HAV3;Smart PV inverter, Smart PV Controller, Cascading, Smart I-V Curve Diagnosis

M:SUN2000-196KTL-H0,SUN2000-200KTL-H2,SUN2000-215KTL-H0;HAV3;Smart PV inverter, Smart PV Controller, Cascading, Smart I-V Curve Diagnosis

Technical Specifications

Technical Specifications

Efficiency

Item

SUN2000-196KTL-H0

SUN2000-200KTL-H2

SUN2000-215KTL-H0

Maximum efficiency

≥ 99.0%

≥ 99.0%

≥ 99.0%

Chinese efficiency

≥ 98.4%

-

-

European efficiency

-

≥ 98.8%

≥ 98.8%

Input

Item

SUN2000-196KTL-H0

SUN2000-200KTL-H2

SUN2000-215KTL-H0

Maximum input voltage

1500 V

Maximum input current (per MPPT)

30 A

Maximum short-circuit current (per MPPT)

50 A

Maximum backfeed current to the PV array

0 A

Minimum operating voltage/startup voltage

500 V/550 V

MPP voltage range

500–1500 V

Full-load MPPT voltage range

930–1300 V

Rated input voltage

1080 V

Number of inputs

18

Number of MPPT circuits

9

Output

Item

SUN2000-196KTL-H0

SUN2000-200KTL-H2

SUN2000-215KTL-H0

Rated active power

196 kW

185 kW

200 kW

Maximum apparent power

216 kVA

215 kVA

215 kVA

Maximum active power (cosφ = 1)

216 kW

215 kW

215 kW

Rated output voltage

800 V AC, 3W+PE

800 V AC, 3W+PE

800 V AC, 3W+PE

Rated output current

141.5 A

133.6 A

144.4 A

Supported power grid frequency

50 Hz

50 Hz/60 Hz

50 Hz/60 Hz

Maximum output current

155.9 A

155.2 A

155.2 A

Power factor

0.8 leading to 0.8 lagging

0.8 leading to 0.8 lagging

0.8 leading to 0.8 lagging

Maximum total harmonic distortion (rated power)

< 3%

< 3%

< 3%

Protection

Item

SUN2000-196KTL-H0

SUN2000-200KTL-H2

SUN2000-215KTL-H0

Input DC switch

Supported

Anti-islanding protection

Supported

Output overcurrent protection

Supported

Input reverse connection protection

Supported

PV string fault detection

Supported

DC surge protection

Type II

AC surge protection

Type II

Insulation resistance detection

Supported

Residual current monitoring unit (RCMU)

Supported

Overvoltage category

PV II/AC III

Typical Noise Value

Item

SUN2000-196KTL-H0

SUN2000-200KTL-H2

SUN2000-215KTL-H0

Typical noise value

65 dB(A)

The typical noise value is the test result obtained under typical working conditions in a lab. To avoid complaints, do not install the inverter in a noise-sensitive area.

Display and Communication

Item

SUN2000-196KTL-H0

SUN2000-200KTL-H2

SUN2000-215KTL-H0

Display

LED indicator; USB data cable + App

RS485

Supported

MBUS

Supported

USB

Supported

General Specifications

Item

SUN2000-196KTL-H0

SUN2000-200KTL-H2

SUN2000-215KTL-H0

Dimensions (W x H x D)

1035 mm x 700 mm x 365 mm

Net weight

84 kg

≤ 86 kg

≤ 86 kg

Operating temperature

–25ºC to +60ºC

Cooling mode

Smart air cooling

Maximum operating altitude

5000 m (derated when the altitude is greater than 4000 m)

Relative humidity

0%–100% RH

Input terminal

MC4 EVO2

Output terminal

Waterproof terminal+OT/DT terminal

IP rating

IP66

Topology

Transformerless

Translation
Favorite
Download
Update Date:2025-09-01
Document ID:EDOC1100141536
Views:361819
Downloads:17313
Average rating:1.0Points

Digital Signature File

digtal sigature tool