SUN2000-(8KTL-20KTL)-M2 User Manual
M:SUN2000-8KTL-M2,SUN2000-10KTL-M2,SUN2000-12KTL-M2,SUN2000-15KTL-M2,SUN2000-17KTL-M2,SUN2000-20KTL-M2;Smart PV inverter, Smart PV Controller, Cascading, AFCI, dry contact scheduling, dry contact function, IPS self-check, rapid shutdown
M:SUN2000-8KTL-M2,SUN2000-10KTL-M2,SUN2000-12KTL-M2,SUN2000-15KTL-M2,SUN2000-17KTL-M2,SUN2000-20KTL-M2;Smart PV inverter, Smart PV Controller, Cascading, AFCI, dry contact scheduling, dry contact function, IPS self-check, rapid shutdown
Resetting Password
- Ensure that the SUN2000 connects to the AC and DC power supplies at the same time. Indicators
and
are steady green or blink at long intervals for more than 3 minutes.
- Perform the following operations within 4 minutes:
- Turn off the AC switch and set the DC switch at the bottom of the SUN2000 to OFF. Wait until all the LED indicators on the SUN2000 panel turn off.
- Turn on the AC switch, set the DC switch to ON, and wait for about 90s. Ensure that the indicator
is blinking green slowly.
- Turn off the AC switch and set the DC switch to OFF. Wait until all LED indicators on the SUN2000 panel are off.
- Turn on the AC switch and set the DC switch to ON.
- Reset the password within 10 minutes. (If no operation is performed within 10 minutes, all inverter parameters remain unchanged.)
- Wait until the indicator
blinks green at long intervals.
- Obtain the initial WLAN hotspot name (SSID) and initial password (PSW) from the label on the side of the SUN2000 and connect to the app.
- On the login screen, set a new login password and log in to the app.
Figure D-1 Setting the password - Wait until the indicator
- Set router and management system parameters to implement remote management.
Document ID:EDOC1100150830
Views:196771
Downloads:8306
Average rating:2.67Points