Atlas 900 Compute Node iBMC Alarm Handling 04
ALM-0x23000007 Failed to Read the Temperature of the Middle of the Air Inlet of the I/O Board (I/O Board, Minor Alarm)
Description
Alarm message:
Failed to obtain data of the middle part of the I/O board(arg1) air inlet temperature.
This alarm is generated when the system failed to obtain the air inlet temperature in the middle part of the I/O board.
Alarm object: I/O board
Impact on the System
The temperature cannot be monitored. No alarm will be reported when the temperature is not in the normal range.
Procedure
- Restart the iBMC. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 2.
- Remove the power cable to power off the server, and then reconnect the power cable to power on the server. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 3.
- Replace the I/O board. Then, check whether the alarm is cleared.
If yes, no further action is required.
If no, go to 4.
- Contact technical support.