SUN2000-(125KTL-M5, 200KTL-H4, 250KTL-H0, 286KTL-H0) User Manual

M:SUN2000-125KTL-M5,SUN2000-200KTL-H4,SUN2000-250KTL-H0,SUN2000-286KTL-H0;Smart PV inverter, Smart PV Controller, Cascading

M:SUN2000-125KTL-M5,SUN2000-200KTL-H4,SUN2000-250KTL-H0,SUN2000-286KTL-H0;Smart PV inverter, Smart PV Controller, Cascading

Technical Specifications

Technical Specifications

Efficiency

Item

SUN2000-200KTL-H4

SUN2000-250KTL-H0

SUN2000-286KTL-H0

SUN2000-125KTL-M5

Maximum efficiency

99.05%

99.05%

99.05%

98.80%

European efficiency

98.85%

-

98.85%

-

Chinese efficiency

-

98.64%

-

98%

DC Side

Item

SUN2000-200KTL-H4

SUN2000-250KTL-H0

SUN2000-286KTL-H0

SUN2000-125KTL-M5

Number of inputs

2

Number of MPPTs

1

Maximum input voltage

1500 V

1500 V

1500 V

1000 V

Maximum DC input short-circuit current

500 A

500 A

500 A

400 A

Minimum startup voltage[1]

1035 V (690 V)

1080 V (720 V)

1035 V

1035 V (690 V)

1080 V (720 V)

470 V (315 V)

550 V (360 V)

Full-load MPPT voltage range

1015–1300 V (690 V)

1060–1300 V (720 V)

1015–1300 V

1015–1300 V (690 V)

1060–1300 V (720 V)

500–750 V (315 V)

550–750 V (360 V)

MPPT voltage range

1010–1500 V (690 V)

1050–1500 V (720 V)

1010–1500 V

1010–1500 V (690 V)

1050–1500 V (720 V)

470–1000 V (315 V)

530–1000 V (360 V)

Rated input voltage

1015 V (690 V)

1060 V (720 V)

1015 V

1015 V (690 V)

1060 V (720 V)

500 V (315 V)

550 V (360 V)

Note [1]: minimum DC voltage for grid connection under the rated output voltage

Power Grid Side

Item

SUN2000-200KTL-H4

SUN2000-250KTL-H0

SUN2000-286KTL-H0

SUN2000-125KTL-M5

Rated output voltage

690 V/720 V

690 V

690 V/720 V

315 V

360 V

Rated output power

250 kW at 40ºC (690 V)

260 kW at 40ºC (720 V)

250 kW at 40°C

250 kW at 40ºC (690 V)

260 kW at 40ºC (720 V)

125 kW (315 V)

142.8 kW (360 V)

Maximum apparent power

275 kVA (690 V)

286 kVA (720 V)

275 kVA

275 kVA (690 V)

286 kVA (720 V)

137.5 kVA (315 V)

157 kVA (360 V)

Maximum active power

275 kW (690 V)

286 kW (720 V)

275 kW

275 kW (690 V)

286 kW (720 V)

137.5 kW (315 V)

157 kW (360 V)

Rated output current

209.2 A (690 V)

208.5 A (720 V)

209.2 A

209.2 A (690 V)

208.5 A (720 V)

229.1 A

Maximum output current

230.1 A

230.1 A

230.1 A

252.0 A

Supported power grid frequency

50 Hz/60 Hz

50 Hz

50 Hz/60 Hz

50 Hz

Power factor

0.8 leading to 0.8 lagging

Maximum total harmonic distortion (rated power)

< 1%

< 1%

< 1%

< 3%

Protection

Item

SUN2000-200KTL-H4

SUN2000-250KTL-H0

SUN2000-286KTL-H0

SUN2000-125KTL-M5

Overvoltage category

DC II/AC III

DC surge protection

Type II

AC surge protection

Type II

Ground fault protection

Supported

Insulation resistance detection

Supported

Anti-islanding protection

Supported

Output overcurrent protection

Supported

Residual current monitoring unit (RCMU)

Supported

Input reverse connection protection

Supported

Input backfeed protection

Supported

Display and Communication

Item

SUN2000-200KTL-H4

SUN2000-250KTL-H0

SUN2000-286KTL-H0

SUN2000-125KTL-M5

Display

LED indicators

Ethernet

Supported

RS485

Supported

USB

Supported

General Specifications

Item

SUN2000-200KTL-H4

SUN2000-250KTL-H0

SUN2000-286KTL-H0

SUN2000-125KTL-M5

Dimensions (W x H x D)

925 mm x 820 mm x 365 mm

Net weight

< 99 kg

Operating temperature

–25°C to +60°C (derated at +40°C or higher)

–30°C to +60°C (derated at +40°C or higher)

–25°C to +60°C (derated at +40°C or higher)

–30°C to +60°C

Cooling mode

Smart air cooling

Maximum operating altitude

4000 m (derated when the altitude is greater than 2000 m)

Relative humidity

0%–100% RH

AC/DC terminal

OT/DT terminal

IP rating

IP66

Topology

Transformerless