SUN2000-(62.5KTL, 125KTL)-NHM0 User Manual
M:SUN2000-62.5KTL-NHM0,SUN2000-125KTL-NHM0;HB;Smart PV inverter, Smart PV Controller, Cascading
M:SUN2000-62.5KTL-NHM0,SUN2000-125KTL-NHM0;HB;Smart PV inverter, Smart PV Controller, Cascading
Setting Parameters
Setting Grid Parameters
Procedure
- Choose to set grid parameters.
Parameters
No. |
Parameter |
Description |
---|---|---|
1 |
Set this parameter based on the grid code of the country or region where the device is used. |
|
2 |
voltage level |
Specifies the rated voltage corresponding to the current grid code. |
3 |
frequency level |
Specifies the frequency corresponding to the current grid code. |
4 |
Specifies supported power grid types. |
|
5 |
Specifies the device grounding status at the DC side and the connection to the power grid. |
|
6 |
Specifies whether to allow the device to automatically start after the power grid recovers. |
|
7 |
Specifies the time after which the device begins restarting following recovery of the power grid. |
|
8 |
Specifies whether to allow the device to quickly start after the power grid recovers from a short-time failure. |
|
9 |
In order to comply with the standards of certain countries and regions, the device should not disconnect from the power grid in cases where the grid experiences a short-time failure. After the fault is rectified, the output power of the device must be quickly restored. |
|
10 |
Specifies the time required for gradual power increase when the device restarts following power grid recovery. |
|
11 |
According to the standards of certain countries and regions, initial grid connection is not allowed when the grid voltage is higher than the maximum voltage for grid connection. |
|
12 |
According to the standards of certain countries and regions, initial grid connection is not allowed when the grid voltage is below the minimum voltage for grid connection. |
|
13 |
According to the standards of certain countries and regions, initial grid connection is not allowed when the grid frequency is higher than the maximum frequency for grid connection. |
|
14 |
According to the standards of certain countries and regions, initial grid connection is not allowed when the grid frequency is below the minimum frequency for grid connection. |
|
15 |
According to the standards of certain countries and regions, grid reconnection is not allowed when the grid voltage is higher than the maximum grid voltage for grid reconnection. |
|
16 |
According to the standards of certain countries and regions, grid reconnection is not allowed when the grid voltage is below the minimum grid voltage for grid reconnection. |
|
17 |
According to the standards of certain countries and regions, grid reconnection is not allowed when the grid frequency is higher than the maximum grid frequency for grid reconnection. |
|
18 |
According to the standards of certain countries and regions, grid reconnection is not allowed when the grid frequency is below the minimum grid frequency for grid reconnection. |
|
19 |
Specifies the time after which the device begins restarting following the power grid recovery. |
Setting Protection Parameters
Procedure
- Choose Settings > Protection parameters to set protection parameters.
Parameters
No. |
Category |
Parameter |
Description |
---|---|---|---|
1 |
To ensure its safety, the device detects the insulation resistance of the DC side to the ground when it starts a self-check. If the detected value is less than the preset value, the device does not connect to the grid. |
||
2 |
Specifies whether to enable the active islanding protection function. |
||
3 |
Specifies whether to enable the passive islanding protection function. |
||
4 |
Specifies the device protection threshold when the power grid voltage is unbalanced. |
||
5 |
The Japanese standard requires that during passive islanding detection, protection should be triggered if an abrupt voltage phase change is detected. |
||
6 |
The standards of certain countries and regions require the device be protected when the phase angle offset of the power grid three phases exceeds a certain value. |
||
7 |
Specifies the 10-minute undervoltage protection threshold. |
||
8 |
Specifies the 10-minute undervoltage protection duration. |
||
9 |
Specifies the 10-minute overvoltage protection threshold. |
||
10 |
Specifies the 10-minute overvoltage protection duration. |
||
11 |
Specifies the level-N grid overvoltage protection threshold. |
||
12 |
Specifies the level-N grid overvoltage protection duration. |
||
13 |
Specifies the level-N grid undervoltage protection threshold. |
||
14 |
Specifies the level-N grid undervoltage protection duration. |
||
15 |
If this parameter is set to Enable, the device is protected when the power grid frequency changes too fast. |
||
16 |
Specifies the frequency change rate protection threshold. |
||
17 |
The device is protected when the grid frequency change duration exceeds the value. |
||
18 |
Specifies the level-N grid overfrequency protection threshold. |
||
19 |
Specifies the level-N grid overfrequency protection duration. |
||
20 |
Specifies the level-N grid underfrequency protection threshold. |
||
21 |
Specifies the level-N grid underfrequency protection duration. |
N is 1, 2, 3, 4, 5, or 6.
Setting Feature Parameters
Procedure
- Choose to set feature parameters.
Parameters
No. |
Category |
Parameter |
Description |
Remarks |
---|---|---|---|---|
1 |
Specifies the duration for determining communication interruption between the device and the SmartLogger. |
- |
||
2 |
The standards of certain countries and regions require the device to shut down after communication is interrupted for a set period. |
If this parameter is set to Enable, the device automatically shuts down after the communication interruption duration is reached. |
||
3 |
If this parameter is set to Enable, the device automatically starts after communication recovers. If this parameter is set to Disable, the device needs to be started manually after communication recovers. |
This parameter is displayed when the automatic shutdown upon communication interruption is set to Enable. |
||
4 |
If this parameter is set to Enable, the device performs protection according to the set power when communication between the device and the SmartLogger is interrupted for a period longer than Communication disconnection detection time. |
- |
||
5 |
Specifies the fail-safe detection time for disconnection between the device and the SmartLogger or Smart Dongle. |
This parameter is displayed when the protection in the case of communication failure is set to Enable. |
||
6 |
Specifies the protection threshold of the active power after communication is interrupted. The value can be a percentage or a fixed value. |
This parameter is displayed when the protection in the case of communication failure is set to Enable. |
||
7 |
Specifies the active power threshold in percentage. |
This parameter is displayed when the protection in the case of communication failure is set to Enable and Active power threshold when communication fails is set to a percentage. |
||
8 |
Specifies the active power threshold as a fixed value. |
This parameter is displayed when the protection in the case of communication failure is set to Enable and Active power threshold when communication fails is set to a fixed value. |
||
9 |
Specifies the protection threshold of the reactive power after communication is interrupted, including Q/S and power factor. |
This parameter is displayed when the protection in the case of communication failure is set to Enable. |
||
10 |
Specifies the Q/S threshold of the reactive power (%) |
This parameter is displayed when the protection in the case of communication failure is set to Enable and Reactive power threshold when communication fails is set to Q/S. |
||
11 |
Specifies the power factor threshold of the reactive power (PF) |
This parameter is displayed when the protection in the case of communication failure is set to Enable and Reactive power threshold when communication fails is set to Power factor. |
||
12 |
Specifies the duration required for gradual power increase when the device starts. |
- |
||
13 |
Specifies the power change rate when the device shuts down. |
- |
||
14 |
If this parameter is set to Enable, the device shuts down after receiving the 0% power limit command. If this parameter is set to Disable, the device does not shut down after receiving the 0% power limit command. |
- |
||
15 |
The device performs the monitoring function at night. If this parameter is set to Enable, the monitoring function of the device will hibernate at night to reduce power consumption. |
- |
||
16 |
This parameter is mainly used in upgrade scenarios where the power supply at DC side is disconnected. |
After the upgrade starts, if Upgrade delay is set to Enable, the upgrade package is loaded first. After the DC side power supply recovers and the activation conditions are met, the device automatically activates the upgrade. |
||
17 |
RCD enhancement |
RCD enhancement |
RCD refers to the residual current of the inverter to the ground. To ensure device and personal safety, RCD should be limited to the specified value in the standard. If an AC switch with a residual current detection function is installed outside the inverter, this function should be enabled to reduce the residual current generated when the inverter is running, thereby preventing the AC switch from misoperations. |
- |
18 |
PID compensation direction |
PID compensation direction |
When the external PID module compensates the PID voltage for the PV system, set PID compensation direction to the actual compensation direction of the PID module so that the inverter can output reactive power at night. |
This parameter is displayed when PV module type is set to Crystalline silicon. Select PV–positive offset for P-type PV modules. Select PV+ negative offset for N-type PV modules. |
19 |
Power quality optimization mode |
Power quality optimization mode |
If this parameter is set to Enable, the inverter output current harmonics will be optimized. |
- |
20 |
PID protection at night |
PID protection at night |
When the inverter outputs reactive power at night and this parameter is set to Enable, the inverter will shut down automatically if it detects abnormal status of the PID compensation. |
- |
21 |
HVRT is short for high voltage ride-through. When the grid voltage is abnormally high for a short time, the device cannot disconnect from the power grid immediately and must continue to operate for some time. |
- |
||
22 |
Specifies the threshold for triggering HVRT. The threshold settings should meet the local grid standard. |
This parameter is displayed when HVRT is set to Enable. |
||
23 |
During HVRT, the device must generate positive-sequence reactive power to support the power grid. This parameter is used to set the positive-sequence reactive power generated by the device. For example, if you set HVRT gradient K1 to 2, the increment of positive-sequence reactive current generated by the device is 20% of the rated current when the AC voltage increases by 10% during HVRT. |
|||
24 |
During HVRT, the device must generate negative-sequence reactive power to support the power grid. This parameter is used to set the negative-sequence reactive power generated by the device. For example, if you set HVRT gradient K2 to 2, the increment of negative-sequence reactive current generated by the device is 20% of the rated current when the AC voltage increases by 10% during HVRT. |
|||
25 |
LVRT is short for low voltage ride-through. When the grid voltage is abnormally low for a short time, the device cannot disconnect from the power grid immediately and must continue to operate for some time. |
- |
||
26 |
Specifies the threshold for triggering LVRT. The threshold settings should meet the local grid standard. |
This parameter is displayed when LVRT or HVRT is set to Enable.
|
||
27 |
During LVRT, the device must generate positive-sequence reactive power to support the power grid. This parameter is used to set the positive-sequence reactive power generated by the device. For example, if you set LVRT gradient K1 to 2, the increment of positive-sequence reactive current generated by the device is 20% of the rated current when the AC voltage decreases by 10% during HVRT. |
|||
28 |
During LVRT, the device must generate negative-sequence reactive power to support the power grid. This parameter is used to set the negative-sequence reactive power generated by the device. For example, if you set LVRT gradient K2 to 2, the increment of negative-sequence reactive current generated by the device is 20% of the rated current when the AC voltage decreases by 10% during HVRT. |
|||
29 |
Specifies the active current proportional coefficient before and during LVRT. |
|||
30 |
During LVRT, the device is required to limit the reactive current. For example, if you set Percentage of LVRT reactive current limiting to 50, the reactive current upper limit of the device is 50% of the rated current during LVRT. |
|||
31 |
When Zero current due to power grid fault is enabled, if the power grid voltage is less than the value of Threshold of LVRT zero-current mode during LVRT, the zero current mode is used. Otherwise, the mode configured in LVRT mode is used. |
|||
32 |
Sets LVRT mode. The options are Zero-current mode, Constant current mode, Reactive power priority mode, and Active power priority mode. |
|||
33 |
Specifies the low voltage ride-through capability of the device. |
- |
||
34 |
Specifies whether to shield the undervoltage protection function during LVRT or HVRT. |
This parameter is displayed when LVRT or HVRT is set to Enable. |
||
35 |
Specifies the LVRT/HVRT recovery threshold. |
|
||
36 |
Specifies the percentage of the maximum active current to the rated current during fault ride-through (FRT). |
- |
||
37 |
Specifies the recovery rate when the active current recovers to the value at the moment before FRT. |
- |
||
38 |
Specifies whether to enable the Zero current due to power grid fault function. |
- |
||
39 |
This parameter can only be set for the VDE4120. |
- |
||
40 |
Voltage rise suppression |
The standards of certain countries and regions require that when the output voltage exceeds a certain value, the device must suppress a rise in voltage by outputting reactive power and reducing active power. |
- |
|
41 |
The standards of certain countries and regions require the device to generate a certain amount of reactive power when the output voltage exceeds a certain value. |
|
||
42 |
The standards of certain countries and regions require the active power of the device to be derated by a certain slope when the output voltage exceeds a certain value. |
- |
||
43 |
The device adjusts P/Pn (the ratio of the active power to the rated power) in real time based on U/Un(%) (the ratio of the actual power grid voltage to the rated power grid voltage). |
- |
||
44 |
Specifies the time from the response to the end of the adjustment based on the P-U curve. |
- |
||
45 |
The standards of certain countries and regions require that if the power grid frequency fluctuates around a certain value, the device needs to fine-tune the active power output based on the frequency regulation ratio to help stabilize the power grid frequency. In this case, set this parameter to Enable. |
- |
||
46 |
Specifies the adjustment ratio of the active power output. |
This parameter is displayed when the frequency regulation control is set to Enable. |
||
47 |
Specifies the threshold for triggering the frequency regulation control. For example, if this parameter is set to 0.1 Hz, the frequency regulation control is not triggered when the frequency is within reference frequency±0.1 Hz. |
- |
||
48 |
Specifies the active power change gradient of frequency regulation. |
- |
||
49 |
Specifies the upper limit for active power adjustment of frequency regulation. |
- |
||
50 |
Specifies the delay response time of frequency regulation. |
- |
||
51 |
If this parameter is set to Enable, the active power of the device will be derated according to a certain slope when the grid frequency exceeds the frequency that triggers overfrequency-caused derating. |
- |
||
52 |
Specifies the frequency threshold for cutting off overfrequency-caused derating. |
|
||
53 |
Specifies the power threshold for cutting off overfrequency-caused derating. |
|||
54 |
The standards of certain countries and regions require the output active power of devices to be derated when the power grid frequency exceeds a certain value. |
|||
55 |
Specifies the frequency threshold for exiting overfrequency-caused derating. |
|||
56 |
Specifies the decrease rate of the overfrequency-caused derating power. |
|||
57 |
Specifies the power recovery rate of the overfrequency-caused derating. |
|||
58 |
Specifies the frequency detection filter time. |
- |
||
59 |
Specifies the exiting delay time after the frequency reaches the quit frequency of overfrequency-caused derating. |
- |
||
60 |
Specifies the effective delay time of overfrequency-caused derating when the frequency reaches the trigger frequency of overfrequency-caused derating. |
- |
||
61 |
Specifies whether to enable overfrequency-caused derating hysteresis. |
- |
||
62 |
The standards of certain countries and regions require that when the power grid frequency is lower than the frequency threshold for power raising, the device needs to increase the active power output to help increase the power grid frequency. In this case, set this parameter to Enable. |
- |
||
63 |
Specifies the power recovery rate of underfrequency-caused raising. |
This parameter is displayed when the power raising caused by underfrequency is set to Enable. |
||
64 |
Specifies the frequency threshold for stopping underfrequency-caused raising. |
|||
65 |
Specifies the power threshold for stopping underfrequency-caused raising. |
|||
66 |
Specifies the frequency threshold for power raising. |
|||
67 |
Specifies the exit frequency of power raising caused by underfrequency. |
|||
68 |
Delay of underfrequency-caused power raising |
Specifies the delay from the time when the underfrequency power raising function is triggered to the time when the function takes effect. |
Setting Power Adjustment Parameters
Procedure
- On the home screen, tap Power adjustment to go to the parameter setting screen.
Parameters
No. |
Category |
Parameter |
Description |
Remarks |
---|---|---|---|---|
1 |
If this parameter is set to Enable, the device responds to the scheduling instruction from the remote port. If this parameter is set to Disable, the device does not respond to the scheduling instruction from the remote port. |
- |
||
2 |
Specifies the validity period of the scheduling instruction. |
When this parameter is set to 0, the scheduling instruction takes effect permanently. |
||
3 |
Plant active power gradient |
Specifies the rate of active power rise due to sunlight changes. |
- |
|
4 |
Average active power filtering time (ms) |
Specifies the period of active power rise due to sunlight changes. This parameter is used with Plant active power gradient. |
- |
|
5 |
Specifies the change rate of the device's active power. |
- |
||
6 |
Specifies the fixed active power of the device. |
- |
||
7 |
Specifies the active power of the device in percent. |
- |
||
8 |
Specifies the change rate of the device's reactive power. |
- |
||
9 |
Specifies the power factor of the device. |
- |
||
10 |
Specifies the reactive power of the device. |
- |
||
11 |
Night-time reactive power output |
Night-time reactive power output |
In some specific application scenarios, a power grid company requires that the inverter can perform reactive power compensation at night to ensure that the power factor of the local power grid meets requirements. |
This parameter is displayed when Isolation settings is set to Input ungrounded, with TF. |
12 |
Enable reactive power parameters at night |
When this parameter is set to Enable, the inverter outputs reactive power based on the setting of Reactive power compensation at night. Otherwise, the inverter executes the remote scheduling command. |
This parameter is displayed when Night-time reactive power output is set to Enable. |
|
13 |
Night-time reactive power compensation (kVar) |
During the reactive power compensation at night, the reactive power is scheduled by fixed value. |
This parameter is displayed when Night-time reactive power output and Enable reactive power parameters at night are set to Enable. |
|
14 |
The device adjusts Q/S (the ratio of the output reactive power to apparent power) in real time based on U/Un(%) (the ratio of the actual power grid voltage to the rated power grid voltage). |
- |
||
15 |
Specifies the reactive power compensation mode of the device output. |
- |
||
16 |
Specifies the delay time for Q-U adjustment. |
- |
||
17 |
Specifies the reference apparent power in percent. When the actual apparent power of the device is greater than the value of this parameter, the Q-U characteristic curve scheduling function is enabled. |
- |
||
18 |
Specifies the P/Pn when the device exits the Q-U scheduling. |
- |
||
19 |
Specifies the minimum power factor for Q-U adjustment. |
- |
||
20 |
The device adjusts Q/Pmax (the ratio of the reactive power to the maximum active power) in real time based on P/Pmax (the ratio of the active power to the maximum active power). |
- |
||
21 |
The device adjusts the power factor in real time based on U/Un(%) (the ratio of the actual power grid voltage to the rated power grid voltage). |
- |
||
22 |
Specifies the time for filtering the grid voltage in the PF-U curve. |
- |
||
23 |
The device adjusts the output power factor cosφ in real time based on P/Pn (%). |
- |
||
24 |
Specifies the voltage threshold for triggering reactive power compensation based on the curve. |
- |
||
25 |
Specifies the voltage threshold for exiting reactive power compensation based on the curve. |
- |
||
26 |
Specifies the adjustment time for the reactive power to reach the target value during reactive power adjustment. |
- |