FusionModule2000 Smart Modular Data Center Product Description

C:02231JVP,21013309,21013309-001;M:FusionModule2000

C:02231JVP,21013309,21013309-001;M:FusionModule2000

IT Cabinet

IT Cabinet

An IT cabinet complies with the International Electrotechnical Commission (IEC) 60297-1 standard and provides stable installation space for servers in the smart module, thereby ensuring safe operation of servers.

  • Two rPDUs can be vertically installed at the rear of each cabinet.
  • The position of each U is marked on the vertical mounting bars.
  • The front and rear doors of the cabinet can be locked, and can be unlocked only by using dedicated keys.
  • The cabinet supports a door status sensor and electronic access control.
  • The maximum static load of the cabinet is 2400 kg.
Figure 4-2 IT cabinet
Table 4-2 Cabinet technical specifications

Item

Technical Specifications

Dimensions (H x W x D)

  • 2000 mm x 600 mm x 1100 mm (with castors)
  • 2000 mm x 600 mm x 1200 mm (with castors)
  • 2000 mm x 800 mm x 1200 mm (with castors)
  • 2000 mm x 600 mm x 1100 mm (without castors)
  • 2000 mm x 600 mm x 1200 mm (without castors)
  • 2200 mm x 600 mm x 1200 mm (without castors)
  • 2200 mm x 800 mm x 1200 mm (without castors)

Color

Black (PANTONE426C/RAL9005)

Material

High-intensity class A carbon cold rolled steel plate and zinc-coated steel plate

Air channel

Front-to-rear air channels

Installation space

  • A 2000 mm high cabinet provides 42 U available space.
  • A 2200 mm high cabinet provides 47 U available space.
  • The distance between the front and rear mounting bars can be adjusted for every 25 mm.
    • For a 1200 mm deep cabinet: The maximum depth for installing devices inside the cabinet is 750 mm and can be extended to 850 mm by adjusting the mounting bars.
    • For a 1100 mm deep cabinet: The maximum depth for installing devices inside the cabinet is 700 mm and can be extended to 750 mm by adjusting the mounting bars.
  • Positions for vertically installing two rPDUs are provided in the rear of the cabinet.

Installation mode

Installed on an ESD floor, a base, or a concrete floor

Door opening mode

The front door is a single door, and the rear door is a double one.

IP rating

IP20

Optional cabinet accessories

Cable ring, bottom sealing plate, guide rail, tray, side door panel, and bottom plate