CloudEngine 9800, 8800, and 6800 Series Switches Hardware Description (V300)
This document provides an overall description of the CE6800&8800&9800 series switches hardware that V300R020C00 and later versions, helping you obtain detailed information about each chassis, power module, fan module, card, cable, and pluggable modules for ports.
This document provides an overall description of the CE6800&8800&9800 series switches hardware that V300R020C00 and later versions, helping you obtain detailed information about each chassis, power module, fan module, card, cable, and pluggable modules for ports.
CE8851-32CQ8DQ-P
CE8851-32CQ8DQ-P (02353EGP)
Overview
Item | Details |
---|---|
Description | CE8851-32CQ8DQ-P Switch(32*100GE QSFP28, 8*400G QSFPDD, Without Fan and Power Module) |
Part Number | 02353EGP |
Model | CE8851-32CQ8DQ-P |
First supported version | V300R020C00 |
Other part numbers | 02353EGQ (CE8851-32CQ8DQ-P switch (32*100GE QSFP28, 8*400GE QSFPDD, 2*AC power modules, 6*fan modules, port-side intake)) 02353EGR (CE8851-32CQ8DQ-P switch (32*100GE QSFP28, 8*400GE QSFPDD, 2* AC power modules, 6*fan modules, port-side exhaust)) |
Short Name | CE8851-32CQ8DQ-P |
The switch does not support stacking and USB-based deployment.
Appearance
Figures in the document are for reference only, and the actual appearance of the devices may vary depending on the exact device model.
Version Mapping
The huge hardware mapping data is migrated to the Info-Finder hardware center, where you can easily obtain hardware mapping information.
The Info-Finder hardware center incorporates comprehensive hardware information and mapping data by sales regions, allowing you to quickly find desired information and filter the mapping data for more fine-grained data display.
Components
1. Ground screw |
2. USB port |
3. Console port |
4. ETH management port (RJ45) |
5. Six Fan slots |
6. Two Power supply slots |
7. Thirty-two 100GE SFP28/Thirty-two 200GE SFP56 Ethernet optical ports |
8. Eight 400GE QSFP-DD Ethernet optical ports |
9.Equipment serial number (ESN) and MAC address NOTE:
You can scan the code to view the ESN and MAC address of the switch. |
10. Three port-side mounting holes for mounting brackets |
11. Equipotential bonding Ground screws for a ground cable with a two-hole OT terminal |
12. Four power-supply-side mounting holes for mounting brackets |
- |
- |
- |
Slot Layout
Slot Type | Slot ID | Slot Direction | Remarks |
---|---|---|---|
Power Slots | PWR1, PWR2 | Horizontal |
|
Fan Slots | FAN1 to FAN6 | Horizontal |
|
Indicators
1. System status indicator |
2. Stack master/slave indicator |
3. ID indicator |
4. Service port indicator (200GE/100GE/40GE optical port) |
5. Service port indicator (400GE optical port) |
6. ETH management port indicator |
- |
- |
- |
- |
Silkscreen | Name | Color | Status | Description |
---|---|---|---|---|
SYS | System status indicator | - | Steady off | The system is not running. |
Green | Slow blinking | The system is running normally. | ||
Green | Fast blinking | The system is starting. | ||
Red | Steady on | An exception occurs during device startup. | ||
MST | Stack master/slave indicator | - | Steady off | Reserved function. This function is not enabled. |
ID | ID indicator | - | Steady off | The ID indicator is not used and is off by default. |
Blue | Steady on | The ID indicator can be turned on or off remotely to help field engineers find the device to maintain. | ||
- | Service port indicator (200GE/100GE/40GE optical port) NOTE:
Arrowheads show the positions of ports. A down arrowhead indicates a bottom-row port, and an up arrowhead indicates a top-row port. |
- | Steady off | The port is not connected or has been shut down. |
Green | Steady on | A link has been established on the port. | ||
Green | Blinking | The port is sending or receiving data. | ||
- | Service port indicator (400GE optical port) NOTE:
Arrowheads show the positions of ports. A down arrowhead indicates a bottom-row port, and an up arrowhead indicates a top-row port. |
- | Steady off | The port is not connected or has been shut down. |
Green | Steady on | A link has been established on the port. | ||
Green | Blinking | The port is sending or receiving data. | ||
L/A | Management port indicator | - | Steady off | No link is established on the port. |
Green | Steady on | A link is established on the port. | ||
Green | Blinking | The port is sending or receiving data. |
Ports
Port | Connector Type | Description | Available Components |
---|---|---|---|
200GE/100GE/40GE QSFP56 Optical Port | QSFP56 | Port for inputting and outputting 200GE/100GE/40GE optical signals 1. 100GE ports can be configured as 40GE or 50GE (50GE: 2 x 25GE) ports but cannot be split into 2 x 50GE ports. 2. A 100GE port can be split into 4 x 25GE, 4 x 10GE, or 2 x 50GE (50GE: 2 x 25GE) ports. Ports 1 and 2, 3 and 4, ..., and 31 and 32 form different groups. The two ports in a group need to be split together. For example, ports 1 and 2 form a group. When port 1 is split, port 2 is also split. 200GE ports can be configured as 40GE/100GE ports and can be split into 2 x 100GE (100GE: 2 x 50GE) ports. In V300R020C00, ports 1 and 2 cannot be split, and 200GE ports cannot be split. This restriction does not apply to V300R020C10 and later versions. |
NOTE:
1. Support for optical modules: (1) In the case of port-side air intake, downlink 100GE/200GE ports support 100G-SR4/CWDM4/LR4/4WDM. (2) In the case of port-side air exhaust, downlink 100GE/200GE ports support 100G-SR4/CWDM4. 2. Support for copper cables: When 200GE copper cables are used, contact Huawei engineers for interconnection verification. |
400GE/200GE/100GE/40GE QSFP-DD optical port | QSFP-DD | Port for inputting and outputting 400GE/200GE/100GE/40GE optical signals 1. 400GE ports can be used as 200GE, 100GE, and 40GE ports. 2. In V300R020C10, a 400GE port can be used as a 200GE/100GE/40GE port and can be split into 4 x 100GE (100GE: 2 x 50GE but not 4 x 25GE) ports. Other port split modes, such as 2 x 200GE/2 x 100GE/2 x 40GE/8 x 50GE/8 x 25GE/8 x 10GE/4 x 50GE/4 x 25GE/4 x 10GE, are not supported. In V300R021C10, a 400GE port can be dynamically split into 2 x 200GE ports. Currently, 2 x 200GE AOCs and 2.5 m copper cables can be used. |
NOTE:
1. Support for optical modules: (1) In the case of port-side air intake, uplink 400GE ports support 400G-SR8/SR4/DR4/FR4. When the ambient temperature ranges from 0°C to 35°C (32°F to 95°F), 400G-LR8 is supported. However, the noise of the device exceeds the threshold at room temperature. (2) In the case of port-side air exhaust, uplink 400GE ports support 400G-SR8/SR4. However, the noise of the device exceeds the threshold at room temperature. (3) 400G-VR4 is supported in V300R024C10 and later versions. 2. Support for copper cables: V300R021C10 and later versions: 40GE/100GE/200GE/400GE copper cables are supported. A 400GE port can be dynamically split into 2 x 200GE ports. 2.5 m copper cables can be used. When 200GE and 400GE copper cables are used, contact Huawei engineers for interconnection verification. V300R020C10 and V300R021C00: 40GE/100GE/200GE/400GE copper cables are supported. After uplink ports are split, copper cables are not supported. When 200GE and 400GE copper cables are used, contact Huawei engineers for interconnection verification. V300R020C00: 40GE/100GE copper cables are supported. After a port is split, copper cables are not supported. 200GE/400GE copper cables are not supported. |
Console port | RJ45 | The console port is connected to a console for onsite configuration. The default baud rate is 9600 bit/s. | |
ETH management port | RJ45 | Connected to a network port of a configuration terminal or network management workstation to set up a configuration environment onsite or remotely. | Category-5 or higher category Ethernet cable |
USB port | USB 2.0 Type A | It can be used for log backup and USB-based deployment. This function is reserved. |
2.0 USB flash drive |
Heat Dissipation System
The cooling system of the CloudEngine 8800 series switches uses front-to-back or back-to-front airflow depending on the airflow direction of the power modules and fan modules used.
- Front-to-back airflow: Power modules and fan modules with front-to-back airflow are identified by
. Air flows into the chassis from the power supply side and is exhausted from the port side, as shown in Figure 4-218 (using a CE6866-48S8CQ-P chassis as an example).
- Back-to-front airflow: Power modules and fan modules with back-to-front airflow are identified by
. Air flows into the chassis from the port side and is exhausted from the power supply side, as shown in Figure 4-219 (using a CE6866-48S8CQ-P chassis as an example).
The airflow direction of the power modules and fan modules required on the CloudEngine 8800 series switches depends on how the device is installed in a cabinet. Typically, cabinets in a data center have cold air flowing in from the front and hot air exhausted from the back. If a switch is installed with the power supply side facing the front and the port side facing the back, the switch needs to adopt fan modules and power modules with front-to-back airflow.
Power modules and fan modules using forced air cooling on a switch must have the same airflow direction. If a switch adopts power modules with back-to-front airflow, the switch must use fan modules with back-to-front airflow as well.
Technical Specifications
Item | Specification |
---|---|
Dimensions with packaging (H x W x D) [mm (in.)] | 260 mm x 790 mm x 590 mm (10.24 in. x 31.10 in. x 23.23 in.) |
Dimensions without packaging (H x W x D) [mm (in.)] |
|
Weight without packaging [kg (lb)] | 9.1 kg (excluding optical modules, power modules, and fan modules) |
Weight without packaging (full configuration) [kg (lb)] | 12.2 kg (including AC power modules and fan modules, excluding optical modules) |
Weight with packaging [kg (lb)] | 13.4 kg (29.54 lb) |
Weight with packaging (full configuration) [kg (lb)] | 16.5 kg (36.37 lb) |
Chassis height [U] | 1 U |
Installation Type | Cabinet Installation |
Switching capacity | To obtain data of this specification item, see the corresponding datasheet or contact the product sales personnel. |
CPU | 4-core, 1.4 GHz |
Memory | DRAM: 8 GB |
NOR Flash | 64 MB |
NAND Flash | 4 GB |
USB | It can be used for log backup and USB-based deployment. This function is reserved. |
Power supply mode |
|
Console port | RJ45 |
Downlink Service interface | 32 x 100GE QSFP28/32 x 200GE QSFP56 |
Uplink Service interface | 8 x 400GE QSFP-DD |
Service port supporting the stack function | Reserved function. This function is not enabled. |
RTC | Supported |
Typical power consumption [W] |
|
Typical heat dissipation [BTU/hour] |
|
Static power consumption [W] | 455 W |
Static heat dissipation [BTU/hour] | 1757 BTU/hour |
Maximum power consumption [W] |
|
Maximum heat dissipation [BTU/hour] |
|
Number of power modules | 2 |
Redundant power supply | 1+1 backup |
Rated input voltage [V] |
|
Input voltage range [V] |
|
Maximum input current [A] | 1200 W AC&240 V DC power module:
1200 W DC power module: 38 A |
Rated output power [W] |
|
Certification |
|
Power supply surge protection [kV] | AC power supply protection: 6 kV in common mode and 6 kV in differential mode 240 V HVDC power supply protection: 4 kV in common mode and 2 kV in differential mode –48 V DC power supply protection: 4 kV in common mode and 2 kV in differential mode |
Types of fans | Pluggable |
Number of fan modules | 6 |
Redundant fans | The device supports 5+1 backup of fan modules that work in hot standby mode. The system can operate normally for a short time after a single fan module fails. You are advised to replace the faulty fan module immediately. |
Heat dissipation mode | Air cooling |
Airflow direction | Port-side air intake or port-side air exhaust, depending on the fan modules and power modules that are used. The fan modules and power modules must have the same airflow direction. |
Availability | 0.9999920679 |
MTBF [year] | 21.59 years |
Noise at normal temperature (27°C, sound pressure) [dB(A)] |
|
Noise at high temperature (40°C, sound pressure) [dB(A)] |
|
Long-term operating altitude [m (ft.)] | ≤ 5000 m (16404 ft.) |
Long-term operating relative humidity [RH] | 5% RH to 95% RH, non-condensing |
Long-term operating temperature [°C (°F)] | 0°C to 40°C (32°F to 104°F) at an altitude of 0–1800 m (0–5906 ft.) NOTE:
When the altitude is 1800–5000 m (5096–16404 ft.), the highest operating temperature reduces by 1°C (1.8°F) every time the altitude increases by 220 m (722 ft.). |
Storage altitude [m (ft.)] | ≤ 5000 m (16404 ft.) |
Storage relative humidity [RH] | 5% RH to 95% RH, non-condensing |
Storage temperature [°C (°F)] | -40ºC to +70ºC (-40°F to +158°F) |
RTU License Supported | Yes. By default, 32 100GE ports can work at the rate of 100 Gbit/s, and 400GE ports are unavailable. The following RTU licenses can be used: 88036EUN: Eight 400GE ports are added. 88036EUP: The rate of 32 x 100GE ports is upgraded to 200 Gbit/s. |