Function

The SUN2000 is a three-phase grid-tied PV string inverter that converts the DC power generated by PV strings into AC power and feeds the power to the power grid.

Features

Intelligent

  • 6 independent maximum power point tracking (MPPT) circuits and 12 PV string inputs: Support the flexible configuration of 2+2+2+2+2+2 strings.
  • 12 routes of high-precision smart PV string monitoring: Help identify and rectify exceptions in a timely manner.
  • MBUS networking: Uses the existing power line for communication and does not require an additional communications cable, which reduces the construction and maintenance costs and improving communication reliability and efficiency.
  • Smart I-V curve diagnosis: Implements I-V scanning and health diagnosis for PV strings. In this way, potential risks and faults can be detected in time, improving the plant O&M quality.

Efficient

  • Peak efficiency: 99%
  • CEC efficiency: 98.5%

Safe

  • Arc fault protection (AFCI: arc fault circuit interrupter): UL 1699B Type I
  • Embedded DC and AC SPDs: all-dimensional surge protection
  • Embedded residual current monitoring unit: Immediately disconnects from the power grid upon detecting that the residual current exceeds the threshold.

Reliable

  • Natural cooling
  • No-fuse design
  • Protected to Type 4X
  • Effective design for ground subsidence: The AC terminal block can be pulled down by up to 50 mm (1.97 in.) due to cable overstress.

Networking Application

The SUN2000 applies to distributed grid-tied commercial PV systems and large-scale grid-tied PV plants. Typically, a grid-tied PV system consists of the PV string, SUN2000, AC combiner box, and step-up transformer.

Figure 2-4 Networking application

(A) PV string

(B) SUN2000

(C) AC combiner box

(D) Step-up transformer

(E) Power grid

  

Supported Power Grid Earthing Systems

The following figure shows the power grid earthing systems supported by the SUN2000.

Figure 2-5 Supported power grid

The SUN2000 supports the IT earthing system in PV-only scenario. The use of the SUN2000 in other types of earthing systems, such as TT, TN-C, and TN-C-S, is not recommended. (If such an earthing system is encountered, contact the Company's engineers.)