SUN2000-100KTL-USH0 User Manual
M:SUN2000-100KTL-USH0;HAV2;Smart PV inverter, Smart PV Controller, Cascading, Smart I-V Curve Diagnosis
M:SUN2000-100KTL-USH0;HAV2;Smart PV inverter, Smart PV Controller, Cascading, Smart I-V Curve Diagnosis
Introduction
Function
The SUN2000 is a three-phase grid-tied PV string inverter that converts the DC power generated by PV strings into AC power and feeds the power to the power grid.
Features
Intelligent
- 6 independent maximum power point tracking (MPPT) circuits and 12 PV string inputs: Support the flexible configuration of 2+2+2+2+2+2 strings.
- 12 routes of high-precision smart PV string monitoring: Help identify and rectify exceptions in a timely manner.
- MBUS networking: Uses the existing power line for communication and does not require an additional communications cable, which reduces the construction and maintenance costs and improving communication reliability and efficiency.
- Smart I-V curve diagnosis: Implements I-V scanning and health diagnosis for PV strings. In this way, potential risks and faults can be detected in time, improving the plant O&M quality.
Efficient
- Peak efficiency: 99%
- CEC efficiency: 98.5%
Safe
- Arc fault protection (AFCI: arc fault circuit interrupter): UL 1699B Type I
- Embedded DC and AC SPDs: all-dimensional surge protection
- Embedded residual current monitoring unit: Immediately disconnects from the power grid upon detecting that the residual current exceeds the threshold.
Reliable
- Natural cooling
- No-fuse design
- Protected to Type 4X
- Effective design for ground subsidence: The AC terminal block can be pulled down by up to 50 mm (1.97 in.) due to cable overstress.
Networking Application
The SUN2000 applies to distributed grid-tied commercial PV systems and large-scale grid-tied PV plants. Typically, a grid-tied PV system consists of the PV string, SUN2000, AC combiner box, and step-up transformer.
(A) PV string |
(B) SUN2000 |
(C) AC combiner box |
(D) Step-up transformer |
(E) Power grid |
Supported Power Grid Earthing Systems
The following figure shows the power grid earthing systems supported by the SUN2000.
The SUN2000 supports the IT earthing system in PV-only scenario. The use of the SUN2000 in other types of earthing systems, such as TT, TN-C, and TN-C-S, is not recommended. (If such an earthing system is encountered, contact the Company's engineers.)