Distributed PV Plants Connecting to NetEco 1000S Smart PV Management System User Manual (Commercial Inverters + SmartLogger1000A)

This document describes how to connect the commercial inverter to Huawei NetEco 1000S Smart PV Management System by using the distributed SmartLogger1000A.

This document describes how to connect the commercial inverter to Huawei NetEco 1000S Smart PV Management System by using the distributed SmartLogger1000A.

Setting SmartLogger Parameters (WebUI)

Setting SmartLogger Parameters (WebUI)

Enter https://XX.XX.XX.XX (SmartLogger IP address) in the address box of a browser, log in to the WebUI as Advanced User or Special User, and configure the SmartLogger as instructed by Deployment Wizard. This section is only for check and supplement.

NOTE:
  • Set corresponding parameters as prompted. For details, see Help on the page.
  • The initial password for Advanced User and Special User to log in to the WebUI is Changeme. Use the initial password upon first power-on and change it immediately after login. To ensure account security, change the password periodically and keep the new password in mind. Not changing the initial password may cause password disclosure. A password left unchanged for a long period of time may be stolen or cracked. If a password is lost, devices cannot be accessed. In these cases, the user is liable for any loss caused to the PV plant.
Figure 4-7 Deployment wizard

Prerequisites

  • The SmartLogger and PC have been connected to the network device using Ethernet cables, or the SmartLogger has been connected to a PC using an Ethernet cable.
  • The IP address of the PC has been changed and is in the same network segment as the SmartLogger (default IP address: 192.168.0.10).
Figure 4-8 Connecting the SmartLogger to a PC

Procedure

  1. Enter https://XX.XX.XX.XX (SmartLogger IP address) in the address box of a browser, and log in to the WebUI as Advanced User.

    Figure 4-9 Logging in to the WebUI
    NOTE:

    If WebUI cannot be accessed, specify security settings for the browser. For details, see the SmartLogger1000A User Manual.

  2. Set RS485 communications parameters (RS485-N corresponds to COM port N on the SmartLogger).

    Figure 4-10 Setting RS485 communications parameters

    Parameter

    Description

    Protocol

    Set this parameter based on the protocol of the connected device. Set this parameter to Modbus when connecting to the inverter.

    Baud rate

    Set this parameter based on the baud rate of the connected device.

    Parity

    Set this parameter based on the parity of the connected device.

    Stop Bit

    Set this parameter based on the stop bit of the connected device. Retain the default value 1 when connecting to the inverter.

    Start address

    Retain the default value 1.

    End address

    Retain the default value 247.

  3. Add communications devices connected to the SmartLogger.

    1. Click Auto. Search or Add Devices.
    2. If not all devices are detected due to duplicate communication addresses, click Auto Assign Address to assign and adjust the addresses as prompted.
    Figure 4-11 Automatic address assigning

  4. Set parameters for the communication between the SmartLogger and the management system.

    • Method 1: When the SmartLogger connects to the management system over the 4G/3G/2G network, set mobile data parameters.
    Figure 4-12 Setting mobile data parameters

    Parameter

    Description

    Monthly traffic package

    Set this parameter based on the SIM card package.

    Network mode

    Set this parameter based on the SIM card network mode.

    APN mode

    The default value is Automatic. If the Automatic mode cannot be used to access the Internet, set this parameter to Manual.

    Authentication type

    When APN mode is set to Manual, set the parameters related to the SIM card with the information obtained from the carrier.

    APN

    APN dialup number

    APN user name

    APN user password

    • Method 2: When the SmartLogger connects to the management system over a wired network, set the wired network parameters.
    Figure 4-13 Setting wired network parameters

    Parameter

    Description

    IP address

    Set this parameter based on the PV plant.

    NOTE:

    If the IP address is changed, log in to the system with the new IP address.

    Subnet mask

    Set this parameter based on the actual subnet mask of the LAN where the SmartLogger is located.

    Default gateway

    Set this parameter based on the actual gateway of the LAN where the SmartLogger is located.

    Primary DNS server

    You can ignore this parameter when connecting to the LAN.

    Set this parameter to the IP address of the LAN router when connecting to a public network (for example, in the scenarios of connecting to Huawei Hosting Cloud Center, an email box, or a third-party FTP, the IP address of the server is set to the domain name).

    Secondary DNS server

    In normal cases, you can ignore this parameter.

    If the primary DNS server cannot resolve the domain name, the secondary DNS server is used.

  5. Set server parameters for the management system.

    Figure 4-14 Setting management system parameters

    Parameter

    Description

    Server

    Set this parameter to the IP address or domain name of the management system.

    Port

    Set this parameter to the port number of the management system to which the SmartLogger connects over a network protocol.

    Address mode

    Communication address and Logical address are supported.

    If the communication address of the device connected to the SmartLogger is unique, you are advised to select Communication address. Otherwise, select Logical address.

    SSL encryption

    Retain the default value Enable.

    NOTE:

    If this parameter is set to Disable, the data exchange between the SmartLogger and the management system is not encrypted, which poses security risks.

    Second challenge authentication

    Set this parameter to Enable.

    Security Certificate

    Optional. This item is used only when the certificate expires or the customer needs to use the self-owned certificate.

Translation
Favorite
Download
Update Date:2019-07-18