SUN2000-(125KTL-M5, 200KTL-H4, 250KTL-H0, 286KTL-H0) User Manual

M:SUN2000-125KTL-M5,SUN2000-200KTL-H4,SUN2000-250KTL-H0,SUN2000-286KTL-H0;Smart PV inverter, Smart PV Controller, Cascading

M:SUN2000-125KTL-M5,SUN2000-200KTL-H4,SUN2000-250KTL-H0,SUN2000-286KTL-H0;Smart PV inverter, Smart PV Controller, Cascading

Power Adjustment Parameters

Power Adjustment Parameters

No.

Parameter

Setting Description

Remarks

1

Remote power schedule

If this parameter is set to Enable, the inverter responds to the scheduling instruction from the remote port. If this parameter is set to Disable, the inverter does not respond to the scheduling instruction from the remote port.

-

2

Schedule instruction valid duration (s)

Specifies the time for maintaining the scheduling instruction.

When this parameter is set to 0, the scheduling instruction takes effect permanently.

3

Plant active power gradient

Specifies the rate of active power rise due to irradiance changes.

-

4

Filter duration for average active power

This parameter is used together with Plant active power gradient. When the active power increases due to irradiance changes, the device increases the active power output in a non-linear pattern. This parameter is used to adjust the time step of the active power change.

-

5

Active power change gradient (%/s)

Specifies the change speed of the inverter active power.

This parameter is displayed when Remote power schedule is set to Enable.

6

Active power (kW)

Specifies the active power output of the device by fixed value.

7

Active power (%)

Specifies the active power output of the device by percentage.

8

Reactive power output at night

In some specific application scenarios, a power grid company requires that the device can perform reactive power compensation at night to ensure that the power factor of the local power grid meets requirements.

This parameter is displayed when Isolation is set to Input ungrounded (with TF).

9

Reactive power change gradient (%/s)

Specifies the change speed of the inverter reactive power.

-

10

PF(U) voltage detection filter time (s)

Specifies the time for filtering the grid voltage in the PF-U curve.

-

11

Power factor

Specifies the power factor of the inverter.

-

12

Reactive power compensation (Q/S)

Specifies the reactive power output by the inverter.

-

Translation
Favorite
Download
Update Date:2025-08-30
Document ID:EDOC1100269387
Views:18785
Downloads:716
Average rating:4.0Points

Digital Signature File

digtal sigature tool