2012 String Current Backfeed

2012 String Current Backfeed

Alarm Attribute

Alarm ID

Alarm Name

Alarm Severity

2012

String Current Backfeed

Warning

Possible Cause

Cause ID

Possible Cause

1–28

  1. Only a few PV modules are connected in series in the PV string. Therefore, the terminal voltage is lower than that of other PV strings.
  2. Reverse polarity occurs in the string.

Suggestion

  1. Check whether the number of PV modules connected in series to this PV string is less than the number of PV modules connected in series to the other PV strings connected in parallel with this PV string. If yes, wait until the PV string current drops to below 0.01 A, set DC SWITCH to OFF, and adjust the number of PV modules in the PV string.
  2. Check whether the PV string is shaded.
  3. Check whether the open-circuit voltage of the PV string is normal.
  4. Check whether PV modules in the PV string are connected in reverse polarity.
  5. The following is the mapping between PV strings and alarm cause IDs: [IDs 1–n correspond to PV strings 1–n respectively.]