Inverter Alarm Reference

Inverter,Alarm

Inverter,Alarm

2036 Grid overfrequency

2036 Grid overfrequency

Alarm Attribute

Alarm ID

Alarm Name

Alarm Severity

2036

Grid overfrequency

Major

Possible Cause

Cause ID

Possible Cause

1

Power grid exception: The power grid frequency is higher than the frequency required in the local standard.

Suggestion

  1. If the alarm occurs occasionally, the power grid may be abnormal temporarily. The device automatically recovers after detecting that the power grid becomes normal.
  2. If the alarm occurs frequently, check whether the power grid frequency is within the allowed range. If not, contact the local power operator. If yes, modify the power grid overfrequency protection threshold after obtaining the consent of the local power operator.