(Optional) Installing Power Cables for the Low Temperature Component
- Connect the cable delivered with the low temperature component to the L/N terminal on the QF2 of the outdoor unit.Figure 4-84 Installing power cables for the low temperature component
(1) Power cable between the outdoor unit and the indoor unit
(2) Power cable between the low temperature component and the outdoor unit
(3) Top cable hole
The label is "Receiver heater/Water-cooled module" or "Low temperature component/Water-cooled module". The actual label may vary.
- Connect one end of the 2 x 1.5 mm2 power cable for the low temperature component to terminal L/N on the QF2 of the outdoor unit, and connect the other end to terminal L/N on the low temperature component or water-cooled module of the indoor unit.
- Secure the cable on the post of the cabinet with cable ties.