Setting Parameters for the Slave SmartLogger
- Log in to the slave SmartLogger WebUI, set Modbus TCP parameters, and click Submit.Figure 6-39 Setting Modbus TCP parameters
Parameter
Description
Link setting Set this parameter to Enable(Limited).
Client N IP Address Set this parameter to the IP address of the master SmartLogger.
Address mode The value can be Comm. Address or Logical address.
If the communications address of the device connected to the SmartLogger is unique, you are advised to select Comm. Address. In other cases, you must select Logical address.
SmartLogger address Set this parameter to the communications address of the slave SmartLogger.
Fast scheduling [1]The default value is Enable.
- Set this parameter to Enable to enable the fast scheduling function of the SmartLogger Modbus TCP interface.
- Set this parameter to Disable to disable the fast scheduling function of the SmartLogger Modbus TCP interface.
Note [1]: This parameter can be set only for V300R023C00 and later versions. The fast scheduling function of the Modbus TCP interface is mutually exclusive with the GOOSE fast scheduling function. The fast scheduling function of only one protocol takes effect at a time.
- Log in to the WebUI of the master SmartLogger, set access parameters for the slave SmartLogger, and click Add Devices.Figure 6-40 Setting access parameters
Parameter
Description
Device Type Set this parameter to SmartLogger.
IP address Set this parameter to the IP address of the slave SmartLogger.