SmartLogger3000 User Manual
M:SmartLogger3000
M:SmartLogger3000
Setting ESS Parameters (Model 1)
ESS parameter settings in this section apply to the following models:
- LUNA2000-97KWH-1H1
- LUNA2000-129KWH-2H1
- LUNA2000-161KWH-2H1
- LUNA2000-200KWH-2H0
- LUNA2000-200KWH-2H1
- LUNA2000-1.0MWH-1H1
- LUNA2000-1.0MWH-ES1H1
- LUNA2000-2.0MWH-1H0
- LUNA2000-2.0MWH-1H1
- LUNA2000-2.0MWH-2H0
- LUNA2000-2.0MWH-2H1
- LUNA2000-2.0MWH-4H1
- LUNA2000-2.0MWH-HE2H1
- LUNA2000-2.0MWH-HE1H1
Setting CMU Parameters
This section does not apply to V300R001C00.
Procedure
Choose Submit.
, set running parameters, and clickTemperature and Humidity Control
Parameter |
Description |
---|---|
|
|
Air conditioner parameter setting[1] |
|
At the first startup after deployment or long-term storage, you are advised to start forced dehumidification to reduce the risk of equipment damage caused by condensation. |
|
Note [1]: This parameter can be set only in V300R023C00 and later versions. |
Exhaust Control
Parameter |
Description |
---|---|
Time when the exhaust function is self-tested every day |
|
After the self-test is started, the exhaust fan will be running for a period of time to check its exhaust function. If the exhaust fan does not meet the requirements, the system cannot start. |
|
After started, the exhaust fan will automatically stop in at least 1 hour. If a combustible gas alarm is generated, the exhaust fan cannot be stopped. The exhaust fan cannot be manually started after the fire response is triggered until the fire alarm is cleared or 24 hours later. |
Fire Suppression
Only the LUNA2000-2.0MWH series Smart String Grid Forming ESS supports DC output power distribution.
Parameter |
Description |
---|---|
|
Only the LUNA2000-200KWH series Smart String Grid Forming ESS supports the temperature alarm threshold settings.
Parameter |
Description |
---|---|
Specifies the temperature threshold for triggering a fire alarm and processing fire response logic. |
Burglar Alarm
The burglar alarm function applies only to the C&I scenario. This function is supported only in SmartLogger V300R023C00SPC172 and later versions and shall be used together with LUNA2000B V100R023C00SPC120 and later versions.
Parameter |
Description |
---|---|
Burglar Alarm |
The default value is Disable. Disable: No burglar alarm will be triggered when the ESS door is open. Enable: A burglar alarm will be triggered when the ESS door is open. |
Setting ESU Parameters
This section does not apply to V300R001C00.
Procedure
Choose
, set running parameters, and click Submit.Running Parameters
Parameter |
Description |
---|---|
|
|
Delete battery packs that are not connected. This function is used when replacing battery packs. |
|
After this parameter is set, the system can still monitor the battery for a period of time after power-off. |
|
|
Setting ESC Parameters
This section does not apply to V300R001C00.
Procedure
Choose Submit.
, set running parameters and clickRunning Parameters
Parameter |
Setting Description |
---|---|
To ensure device safety, the device detects the insulation resistance of the DC side to the ground when it starts a self-check. If the detected value is less than the preset value, the device does not start. Value range: [0.05, 1.5]. |
Setting ESR Parameters
This section does not apply to V300R001C00.
Procedure
Choose Submit.
, set running parameters, and clickParameters Settings
Parameter |
Description |
Remarks |
---|---|---|
Set the battery rack to Running or Hibernation. |
- |
|
Set the end-of-charge SOC of battery packs in a battery rack. |
For SmartLogger V300R023C10SPC500 and later versions, Charging cutoff SOC and Discharge cutoff SOC do not take effect. |
|
Set the end-of-discharge SOC of battery packs in a battery rack. |
||
Set the quantity of battery packs in a battery rack. If the quantity is inconsistent with the actual quantity, the system cannot start. |
- |
|
Start or stop the detection for power insulation resistance of the battery rack. |
- |
|
Start or stop the identification for battery pack positions in a battery rack. |
- |
Energy Yield Calibration
Parameter |
Description |
---|---|
Calibrate the total charged energy. |
|
Calibrate the total discharged energy. |
Setting HVAC Parameters
This section does not apply to V300R001C00.
Procedure
Choose Submit.
, set running parameters, and clickParameters Settings
Parameter |
Description |
Remarks |
---|---|---|
The default value is Auto. The air conditioner working mode can be Auto, Dry, Heat, or Cool. |
|
|
Cooling start temperature |
Set the target temperature for cooling when the air conditioner works in automatic mode. |
|
Cooling stop temperature |
Set the target temperature when the air conditioner stops cooling in automatic mode. |
|
Heating start temperature |
Set the target temperature for heating when the air conditioner works in automatic mode. |
|
Heating stop temperature |
Set the target temperature when the air conditioner stops heating in automatic mode. |
|
Set the indoor high temperature alarm threshold for the air conditioner. |
- |
|
Set the indoor low temperature alarm threshold for the air conditioner. |
- |
|
Set the upper threshold for the AC input voltage of the air conditioner. |
This parameter applies only to air conditioners in the battery cabin of the LUNA2000-2.0MWH Series Smart String Grid Forming ESS. |
|
Set the lower threshold for the AC input voltage of the air conditioner. |
This parameter applies only to air conditioners in the battery cabin of the LUNA2000-2.0MWH Series Smart String Grid Forming ESS. |
|
Set the upper threshold for the DC input voltage of the air conditioner. |
This parameter applies only to in-cabinet air conditioners of the LUNA2000-200KWH Series Smart String Grid Forming ESS and air conditioners in the control unit cabin of the LUNA2000-2.0MWH Series Smart String Grid Forming ESS. |
|
Set the lower threshold for the DC input voltage of the air conditioner. |
This parameter applies only to in-cabinet air conditioners of the LUNA2000-200KWH Series Smart String Grid Forming ESS and air conditioners in the control unit cabin of the LUNA2000-2.0MWH Series Smart String Grid Forming ESS. |